Installation
UR46-81/82S
Document number: SG104148TEN
Revision: B01
Issue date: 20.8.2012
Copyright© 2012 Sécheron SA - This document is not contractual and contains information corresponding to the level of technology at the date of release.
C-28
File: c-UR46-8S_inst_en.fm
C.15
Security check advised during operation
The customer should permanently verify that the voltage/current information coming from a
voltage/current detector corresponds to the information about the state of the circuit-breaker
given by its auxiliary contacts (1), according to the complete electrical circuit.
For example, if the information coming from the auxiliary contacts of the circuit-breaker shows
that the circuit-breaker is open and the voltage transformer detect a voltage, this indicates a
serious problem which must be immediately solved.
2767
WARNING!
Never run a vehicle if the information coming from the auxiliary contacts (1) and a
voltage/current detector is contradictory!