Installation
UR46-81/82S
Document number: SG104148TEN
Revision: B01
Issue date: 20.8.2012
Copyright© 2012 Sécheron SA - This document is not contractual and contains information corresponding to the level of technology at the date of release.
C-22
File: c-UR46-8S_inst_en.fm
C.9
Mounting
C.9.1
Mounting position
The circuit-breaker must be installed with the arc chute upside (except when installed in some
optional enclosures).
The arc chute must be screwed on the circuit-breaker.
Fix the circuit-breaker by means of M10 screws (3) or bolts (4), with washers, tightened to a
torque of 44 Nm.
To be able to insert one of the screw (3), the earth bolt (5) needs to be removed and reassem-
bled after (see §
C.11
).
04656
C.9.2
Clearances to be observed in operating position
* Grid with 50% of surface opening.
04612
Important!
The circuit-breaker must be installed in an indoor ventilated enclosure that is free
from dust and moisture (minimum IP54).
Minimum distances to:
A
B
C
(1)
Insulating wall
25
145
350 *
Metal wall
Contact Sécheron
40
23
160
319.5
246
3
5
4
A
A
A
C
B
A
81
82
B