Document number: SG104148TEN
Revision: B01
Issue date: 20.8.2012
Copyright© 2012 Sécheron SA - This document is not contractual and contains information corresponding to the level of technology at the date of release.
File: g-UR46-8S_options_en.fm
G-61
UR46-81/82S
Options
G.4.2
Installation - Electrical connection
BIM5: connect the 6 mm
2
cables (1) coming from the CID-3 into the terminal (2); there is no
recommended polarity.
BIM6: connect both 2.5 mm
2
cables (3) on your device.
03698
G.4.3
Maintenance - J clearance
Refer to the §
G.5
for the procedure.
G.4.4
Maintenance - In case of replacement of the direct release
When removing the direct release in the §
D.12
: remove either the complete BIM5 and BIM6 indi-
rect releases, either only the axle (2) by loosing the screws (7).
G.4.5
Troubleshooting
See the §
G.3.3
.
G.4.6
Spare and wear parts catalogue
03673
Pos.
Part number
WP SP
Description
Qty
1280
HSBA131233R00006
INDIRECT TRIPPING DEVICE BIM5 FOR UR36-
46
1
1290
HSBA131233R0004
INDIRECT TRIPPING DEVICE BIM6 FOR UR36-
46
1
6
HSBA431837P0001
ROD ROUND 12x195-PA6.6 GF30
1
31
HSBA432291P0001
SPACER CY IE M6/13x19 BIM-SS4305
1
32
GON336152P0422
WASHER ELA S 8-ST PHOS B
1
34
SG101204P2
PIPE 9/1.5x15-NBR 65Sh A
1
1
3
2
34
6
32
31
1280
1290
Содержание UR46-81S