Document number: SG104148TEN
Revision: B01
Issue date: 20.8.2012
Copyright© 2012 Sécheron SA - This document is not contractual and contains information corresponding to the level of technology at the date of release.
File: c-UR46-8S_inst_en.fm
C-23
UR46-81/82S
Installation
C.10
Low voltage connector
The connector: Harting 32 poles HAN 32EE.
Sécheron’s number for the mobile connector: SG104063R10100, including 30 pins of 1.5 mm
2
(SC202344) and 2 pins of 2.5 mm
2
(SC201259).
Note!
The mobile connector needs to be ordered separately.
Procedure
a) Insert the cables (5) into the pins (6) according to the following
08007
diagram, using the 09
99 000 0110 crimping tool (with locator) from Harting for HAN E
®
with wire gauges 0.5 -
4 mm
2
.
Note!
The number of the Harting’s pins removal tool is 09 99 000 0319.
b) Manually insert the pins (6) into the holder (7) and fix the holder (7) into the connector (1).
c) Check that the fixed (3) and mobile (1) connectors are not damaged.
d) Connect the mobile connector (1) into the fixed connector (3), ensuring the correct orienta-
tion (pin 1 must go into hole 1 according to the wiring diagram) and that the lock (4) is
correctly locked.
08006
Pins correspondence
08007
The closing coil is connected to pins 21 and 22 (or 31 and 32 for devices manufactured before
spring 2012), regardless of the polarity.
Note!
Up to five double-contact switches (5) can be inserted in the auxiliary housing (6).
1,2
1
4
8
9
3
7
5
6
D
C
15 13
16
12
11 9
7 5
8
3 1
4
19
20
22
21
14
10
6
2
17
18
1
32
Содержание UR46-81S