UR46-81/82S
Introduction
Document number: SG104148TEN
Revision: B01
Issue date: 20.8.2012
Copyright© 2012 Sécheron SA - This document is not contractual and contains information corresponding to the level of technology at the date of release.
File: a-UR46-8S_Intr_en.fm
A-9
A.
Introduction
A.1
General description
A.1.1
Description
The UR46 is a DC high-speed current-limiting circuit-breaker, with natural cooling. It has been
designed to ensure, on detection of a short-circuit, a trip free and rapid opening of its main
contact; and to quickly extinguish the arc by generating a constant over-voltage during the whole
interruption process.
04601
1. Fixed insulating frame made of glass-fibre reinforced insulating material.
2. Main circuit, consisting of a lower connection terminal (21), a moving contact (22), an upper
connection terminal (23) and a fixed contact (24).
3. Over-current release.
4. Arc chute.
5. Closing device and fork.
6. Auxiliary contacts housing with pusher (7).
8. Coolers
A.1.2
Uses of the high speed circuit-breaker
Because of its short response time following the detection of an excess current (short-circuit,
overload detection...), it is particularly suitable for the protection of the DC equipment in traction
substations or industrial installations.
DANGER!
To ensure maximum safety, servicemen and operators must read the
A.2 "Safety
precautions"
section before starting installation, maintenance and adjustment of
the device or before starting to operate it.
8
1
23
21
22
24
3
7
4
5
6
2
Содержание UR46-81S
Страница 68: ...Secheron ...