Replacement of the direct release
Removal
a) Remove the moving contact (1) with the catches: see §
D.7.2 "Replacement of the moving
contact"
.
b) Remove the shock absorber unit (2) and the pusher assembly (3): see §
D.13 "Replacement
of the pusher and the shock absorber"
.
c) Remove the screw (18) and the isolations (19,20).
d) Remove both screws (5) to lower the connecting bar (6).
e) Remove both M8 x 90 screws (7) to lower the direct release (8).
Note!
These screws (7) can also attach an optional indirect release (see §
G.4
).
04635-S
Reassembling
f)
On the new direct release, hand-tighten the nut (9) and lock nut (10) firmly.
g) Attach the direct release (8) onto the frame (11), using both screws (7, attach also the
optional indirect release if present).
h) Insert the lower connecting bar (6) through the frame (11) and the direct release (8). To have
this bar in the correct position, the groove (12) must be upside. Screw in the screws (5) and
hand-tighten them.
i)
Insert the isolations (19,20) between the bar (6) and the support (21), screw in the screw (18)
and hand-tighten it.
j)
Insert the moving contact (1, see §
D.7.2 "Replacement of the moving contact"
) and insert its
pin (14). The moving contact (1) must be located in the centre of the slot (15) and in front of
the fixed contact (16); so adjust it by adjusting the position of the lower connecting bar (6)
before tightening the screws (5,18).
k) Insert the pusher (3) and the shock absorber unit (2) into the frame (11); see §
D.13
"Replacement of the pusher and the shock absorber"
.
l)
Close the breaker and adjust clearance Y: see
D.6.4 "Check and adjustment of the Y clear-
ance"
.
m) In case of an optional indirect release or manual release is present, adjust the J clearance
according to §
G.4 "Indirect releases"
.
Note!
With a new direct release, calibrate the circuit-breaker to determine the new equivalencies
between the maximum current release ld and the adjustment scale. A direct current supply is
needed.