File: d-UR46-8S_maint_en.fm
Grease for general purpose
Shell Rhodina LT2; Sécheron number SG104245P00001.
Cleaning agents
Denatured alcohol.
A solution of liquid soap in water may be used on polyester or polyamide parts on the condition
that these parts are stripped down to the polyester or polyamide parts only for this work and then
rinsed with fresh water and well dried before reassembly.
D.2
Periodicity of the inspections
D.3
Procedure
Perform the following operations:
Important!
No other solvents allowed!
Important!
These frequencies are given for normal (abnormal conditions are listed in §
C.2
).
The user should adapt these frequencies when using this device in other condi-
tions.
Operation
Frequency
Visual inspection
At least once a year
Detailed inspection
Whenever one of the following event occurs first:
– Every 18-24 months
– Or after every 250 overload current interruptions
(current value > maximum current release setting Id).
– Or after every 500 manual or remote openings
(current value < maximum current release setting Id).
Visual inspection
See §
1. Remove the arc chute
D.5.1
2. Perform the visual inspection
D.5.2
3. Refit the arc chute
D.5.3
Detailed inspection
1. Clean the contact area
D.6.1
2. Measure the “W” contact wear dimension
D.6.2
3. Check and adjust the “X” clearance
D.6.3
4. Check and adjust the “Y” clearance
D.6.4
5. Check and adjust the “Z” clearance
D.6.5
6. Check and grease
D.6.6
7. Check and adjust the “J” clearance
G.3.2
/
G.4.3
Содержание UR46-81S