Fig 37: 7-segment display and push buttons IC 4000/1
ON normal working mode DISP1 is blank.
When you need to enter parameter setting:
- Press SW2 and SW3 buttons together for 3
seconds.
- Parameter number “1” is displayed on DISP1.
- Press SW2 to increase the parameter number,
press SW3 to decrease the parameter number.
- When you reached the target parameter
number, press SW2 and SW3 buttons together
for 3 seconds to reach the
setting level for the
value.
- For parameters PP03, PP07, PP08
parameter
number
starts to flash on DISP1.
- For parameters
PP01 und PP02
parameter
value
starts to flash on DISP1.
- Now you can increase the parameter value by
pressing SW2, and decrease it by pressing
SW3.
- To store the new parameter setting, press SW2
and SW3 buttons together for 3 seconds.
- Parameter menu is closed and DISP1 is blank
again.
Parameter settings menu has 10
minutes timeout. If you don’t press
any button for 10 minutes, control
exits from parameters menu
automatically without saving the
settings.
Assignment MODBUS address
For every heater [= burner control unit] it is
mandatory to assign an MODBUS address if it
controlled by SchwankControl Touch.
All heaters are assigned with the MODBUS
address 1 in the delivery state. To change the
MODBUS address, the lid of the IC 4000/1 burner
control unit must be opened.
The MODBUS address is set by the DIP switches
in the lower right side of the board. A maximum
of 31 addresses can be assigned per heating
zone.
Fig 38: MODBUS addressing IC 4000/1 by
DIP switches
Dip switch position below
Dip switch position above
External identification
MODBUS address
For a quick external identification of the
assigned MODBUS address, please enter the
corresponding address [number] on the
provided MODBUS-address label by number
stickers or with marker pen.
MODBUS-address label is to stick on the bottom
side bluTek-burner kit housing.