Flexible exhaust system deltaSchwank [wall terminal]
- version aluminium -
Connection stainless steel flexible pipe
to aluminium tube must be glued with
heat-resistant sealing material and
locked by means of self-tapping
screws.
All socket connections on the exhaust
and incoming air routes must be
locked by means of self-tapping
screws.
The 90° elbow at the sucking fan side is
to mount with the opening on the top.
The wall terminal is mounted with a
small gradient to outside to prevent
intrusion of driving rain.
A vertical distance between exhaust
gas outlet and wall terminal outlet of
at least 50cm is mandatory.
For exhaust gas lengths> 1.5 m
[without wall terminal] condensate
drainage must be installed.
This is valid on principle for types
deltaSchwank 310U and 320U.
Please note the safety distance to
flammable materials:
-
single-wall exhaust pipe: 40 mm
-
double-wall exhaust pipe + wall
terminal: 0 mm
System certification tube heater
deltaSchwank with exhaust line
system MUGRO
CE 0432-CPD-217915,System 0.2 / 0.5
[Muelink&Grol]
The wall terminal is fastened to the
building wall with screws by means
of the integrated flange plate. The
flange plate supports and secures
the wall terminal
.
The following components are required for
mounting the wall terminal aluminum design
[Distance heater- terminal approx. 1.5 m]:
Wall terminal M&G:Article no. 12221797
Testing set C 15-20kW: Article no. 12676660
Testing set C 30-40kW: Article no. 12676750
Fig 8: Position of control points [wall terminal], version aluminium
Control points
exhaust flue:
stainless flexible pipe with
connecting flange
combustion air:
dS 310 - 320U: aluminium pipe
dS 625 - 1260U: stainless flexible pipe
Connection stainless flexible
pipe to aluminium
tube