deltaSchwank
43
Version
002
deltaS
ch
w
ank 19
/18
Tech
ni
cal
sp
eci
fic
ati
on subject to
cha
nge
Parameter IC 4000/1 and setting
The burner control unit IC 4000/1 is already
factory preset.
The parameters can be read out by the
Schwank Service Software IC 4000 [RS-485
interface board] and if necessary to be
changed.
Parameter selection and settings can made
manually direct at IC 4000/1 by the two push
buttons SW 2 and SW 3 and the 7-segment
display.
For this, unscrew the lid of the IC 4000/1 burner
control.
After power supply IC 4000/1 following
sequence is shown on the 7-segment display:
1. segment test, all 7 segments light up
2. software version [two successive numbers]
3. burner control software: 1
Parameter Parameter name and
parameter value definitions
Factory setting
Set range
PP01
Setting Communication
0: No MODBUS control [e.g. ThermoControl M+]
1: MODBUS contol by SchwankControl Touch
1
0 - 1
PP02
Drive Fan
0: Phase angle control driven
1: PWM driven
1
0 -1
PP04
PWM FAN START SPEED
20 – [“PP06 PWM FAN MAX SPEED” or 180]
[Note 1]
xx
according to type
see Tab 5, page 23
20 - 180
PP05
PWM FAN MIN SPEED
20 – [“PP06 Fan PWM FAN MAX SPEED” oder 130]
[Note 2]
xx
according to type
see Tab 5, page 23
20 - 130
PP06
PWM FAN MAX SPEED
[“PP04 PWM FAN START SPEED” or “PP05 PWM MIN
SPEED or 30] –180
[Note 1], [Note 2]
xx
according to type
see Tab 5, page 23
30 - 180
PP09
APS monitoring for PWM driven fan
0: APS disabled for PWM fan
1: APS enabled for PWM fan
0
0 -1
Tab 8: Parameter level IC 4000/1
Note 1:
PP06 >= PP04
Note 2:
PP06 >= PP05