SERVICING THE AT10.1
59
Replacing the Main Control (A1) and/or Gate Driver (A11) PC Boards
For details of this procedure, refer to
Service Instruction
(
JD5012-00
).
NOTICE
Printed circuit boards are sensitive to damage from static discharges. Leave
replacement boards in their anti-static bags until you are ready to install them.
Ground yourself before handling the board, by touching the ground stud on the
back of the door. Always handle printed circuit boards by their edges.
Shut down and lock out all power to the AT10.1. Disconnect the battery
from the output terminals. Remove any optional user wiring from the
various Main Control PC Board (A1) terminals (e.g. TB3, TB8/J6, J3,
etc.).
Note that A1 and A11 are mounted together as a pair. Remove the signal
wire harness plug (J18) at the left edge of A11. The boards are mounted
on ten (10) plastic standoffs. Compress the tab on each standoff, and pull
the boards toward you until they clear all the standoffs. If you are
replacing only one board, carefully separate the existing boards (A1 &
A11) and reconnect the replacement board.
Insert the replacement board(s) onto the instrument panel with the same
orientation, and push them onto the standoffs. Make sure the board is
fully seated on all ten (10) standoffs. Reconnect the signal wire harness
plug (J18) to the Gate Driver PC Board (A11), matching the orientation
when removed. Replace any user wiring to the various Main Control PC
Board (A1) terminals.
See Section 2.1 for the steps to restart the AT10.1. If your AT10.1
parameters (float voltage, etc.) are different from the factory preset values,
you should program in the new values now. See Section 2.3. You should
also recalibrate the dc voltmeter according to Section 2.3.7.
Replacing the ac input or dc output circuit breaker (CB1/CB2)
Shut down and lock out all power to the AT10.1. Remove the Plexiglas
safety shield. Disconnect the battery from the dc output terminals
(TB1+/-). This includes remote sense wires if they were installed.
Check with a voltmeter before proceeding. Remove the mounting screws
for the circuit breaker on the galvanized mounting bracket. Carefully
remove the wired circuit breaker from the AT10.1.
Remove wires from the terminals, one at a time, and transfer the wires to
the terminals of the replacement breaker.
Confirm all circuit breaker
terminal screws are tight
.
Install the replacement breaker into the
mounting bracket, reversing the procedure above, using the original
mounting screws.
Содержание AT10.1 SERIES
Страница 78: ...APPENDIX C 72 Outline AT10 1 Group II Battery Charger NEMA 1 Style 5017 Enclosure JE5025 00...
Страница 79: ...APPENDIX C 73 http www ATSeries net PDFs JE5025 00 pdf...
Страница 80: ...APPENDIX C 74 Outline AT10 1 Group II Battery Charger NEMA 1 Style 5018 Enclosure JE5026 00...
Страница 81: ...APPENDIX C 75 http www ATSeries net PDFs JE5026 00 pdf...
Страница 83: ...APPENDIX C 77 http www ATSeries net PDFs JE5028 99 pdf...
Страница 85: ...APPENDIX C 79 http www ATSeries net PDFs JE5029 99 pdf...
Страница 87: ...APPENDIX C 81 http www ATSeries net PDFs JE5030 29 pdf...
Страница 88: ...APPENDIX C 82 Schematic AT10 1 Group II Battery Charger Standard w o Options JE5032 00...
Страница 89: ...APPENDIX C 83 http www ATSeries net PDFs JE5032 00 pdf...
Страница 90: ...APPENDIX C 84 Schematic AT10 1 Group II Battery Charger w Common Options JE5032 99...
Страница 91: ...APPENDIX C 85 http www ATSeries net PDFs JE5032 99 pdf...
Страница 92: ...APPENDIX C 86 Connection Diagram AT10 1 Group II Battery Charger Standard w o Options JE5034 00...
Страница 93: ...APPENDIX C 87 http www ATSeries net PDFs JE5034 00 pdf...
Страница 94: ...APPENDIX C 88 Connection Diagram AT10 1 Group II Battery Charger w Common Options JE5034 99...
Страница 95: ...APPENDIX C 89 http www ATSeries net PDFs JE5034 99 pdf...
Страница 101: ...USER NOTES 95...