SERVICING THE AT10.1
46
Error
Code
Meaning Repair
Procedure
E 04
internal memory
failure
Any parameters that you set, such as Float or Equalize voltage, are saved
internally. The internal memory is tested on startup. If the memory test
fails,
E 04
appears on the front display. The error may also appear if the
controller was trying to write to the memory while a power failure occured.
If an
E 04
code appears, try shutting down the AT10.1. Restart by turning
on the dc breaker (CB2)
first
, followed by the ac breaker (CB1). If the
AT10.1 restarts normally, you must reenter any changes you made to the
factory settings (float voltage, etc.).
If
E 04
appears repeatedly, the internal memory has been damaged. You
must replace the Main Control PC Board (A1). See Section 3.6 for parts
ordering information.
E 05
not used
This error code was formerly used to indicate a reverse battery
connection. It is not available in the AT10.1.
E 06
defective R4 or
R14 resistor, or
remote sense
wiring failure
Locate R4 and R14 on the Gate Driver PC Board (A11), mounted to the
back side of the front instrument panel. Remove the wire harness plug
from J18, and remove A11 from the Main Control PC Board (A1).
Use an Ohmmeter to measure the values of R4 and R14 (see table 3-1 for
the correct value). If either resistor is not within 1% of the specified value,
the entire Gate Driver PC Board (A11) must be replaced.
If you are using remote sense wiring from the battery to the AT10.1, the
wiring may have failed. The usual failure is an open circuit. A short circuit
will usually be indicated by smoke or fire in the wiring.
The AT10.1 displays the error code if it detects this wiring failure. You
should respond to this problem
quickly
, to make sure the AT10.1
regulates the output voltage properly. Wire an annunciator (e.g. buzzer) to
the summary alarm relay contact (TB3) for remote indication of any
charger problem. Otherwise monitor the AT10.1 operation using the
optional DNP3 Level 2 / Modbus Communications Module (
JA0102-04
).
If a failure exists in remote sense wiring, the AT10.1 regulates its output
voltage locally until you correct the problem, see Sections 1.9. The locally
controlled voltage may not reflect the true requirements of the battery.
When you complete the repair, restart the AT10.1 per Section 2.1.
E 07
open dc
breaker (CB2)
or internal dc
wiring failure
If the dc breaker (CB2) is open, open the ac breaker (CB1). Restart by
closing the dc breaker (CB2)
first
, followed by the ac breaker (CB1). If the
dc breaker trips again, see the troubleshooting chart in Section 3.4.
If the dc breaker (CB2) is closed, but the front panel meter dsiplays
E 07
,
check your battery. If the battery is disconnected, and you
then
disconnect the dc load, the AT10.1 may display an
E 07
code. Restart the
AT10.1 according to Section 2.1.
If the battery and dc load are satisfactory, see the troubleshooting chart in
Section 3.4 for help in locating the problem.
E 08
defective
temperature
compensation
probe
See
Application Note
(
JD5003-00
) for more detailed user instructions.
If a remote temperature compensation probe (A10) is connected to the
AT10.1, the control circuitry detects the probe on startup and uses the
temperature measured by the probe to control the output voltage of the
charger. To understand temperature compensation, see Section 1.11.
If the probe (A10) or the wiring that connects it to the Main Control PC
Board (A1) fails during normal operation, the AT10.1 detects the failure
and displays
E 08
on the front panel meter.
Содержание AT10.1 SERIES
Страница 78: ...APPENDIX C 72 Outline AT10 1 Group II Battery Charger NEMA 1 Style 5017 Enclosure JE5025 00...
Страница 79: ...APPENDIX C 73 http www ATSeries net PDFs JE5025 00 pdf...
Страница 80: ...APPENDIX C 74 Outline AT10 1 Group II Battery Charger NEMA 1 Style 5018 Enclosure JE5026 00...
Страница 81: ...APPENDIX C 75 http www ATSeries net PDFs JE5026 00 pdf...
Страница 83: ...APPENDIX C 77 http www ATSeries net PDFs JE5028 99 pdf...
Страница 85: ...APPENDIX C 79 http www ATSeries net PDFs JE5029 99 pdf...
Страница 87: ...APPENDIX C 81 http www ATSeries net PDFs JE5030 29 pdf...
Страница 88: ...APPENDIX C 82 Schematic AT10 1 Group II Battery Charger Standard w o Options JE5032 00...
Страница 89: ...APPENDIX C 83 http www ATSeries net PDFs JE5032 00 pdf...
Страница 90: ...APPENDIX C 84 Schematic AT10 1 Group II Battery Charger w Common Options JE5032 99...
Страница 91: ...APPENDIX C 85 http www ATSeries net PDFs JE5032 99 pdf...
Страница 92: ...APPENDIX C 86 Connection Diagram AT10 1 Group II Battery Charger Standard w o Options JE5034 00...
Страница 93: ...APPENDIX C 87 http www ATSeries net PDFs JE5034 00 pdf...
Страница 94: ...APPENDIX C 88 Connection Diagram AT10 1 Group II Battery Charger w Common Options JE5034 99...
Страница 95: ...APPENDIX C 89 http www ATSeries net PDFs JE5034 99 pdf...
Страница 101: ...USER NOTES 95...