OPERATING THE AT10.1
32
2.3.3. Setting the Equalize Timer
•
Press the
EDIT/ENTER
key until the
EQLZ HRS REMAINING,
MANUAL TIMER
and
AUTO EQLZ TIMER
indicators light, and the
display flashes the present value of the equalize timer duration in hours.
Press and release the
UP
or
DOWN
key to increase or decrease the value in
the display by one count, or press and hold the
UP
or
DOWN
key to scroll
the value in the display upward or downward. When the meter displays
the desired equalize time (in hours), release the
UP
or
DOWN
key. If you go
past the number of hours you want, press the
UP
or
DOWN
key again to
reach the number you want to set.
If you set the equalize time to zero hours, the equalize mode is disabled
.
•
Press the
EDIT/ENTER
key. The new equalize timer duration is saved
internally. The same timer setting works for both the manual timer and
the auto-equalize timer.
If you want to adjust the alarm settings, skip to Section 2.3.4.
OR
If you want to exit the
Edit Mode
now, press the
EDIT/ENTER
key three (3)
more times until the AT10.1 returns to normal operation.
2.3.4. Setting the Alarms
After you save the equalize timer setting, the
Edit Mode
automatically
prompts you to adjust the settings of the high dc voltage and low dc
voltage alarms. There is a red indicator light on the front instrument panel
of the AT10.1 for each of the following alarm conditions:
•
High DC Voltage
•
Low DC Voltage
•
DC Output Failure
•
AC Input Failure
•
Positive (+) Ground Fault Detection
•
Negative (-) Ground Fault Detection
When an alarm occurs, the indicator LEDs will light immediately. The
AT10.1 also features a summary alarm relay with one (1) form-C remote
contacts (TB3), rated 0.5A / 125 Vac/Vdc. If an alarm condition lasts for
30 seconds or longer, the summary alarm relay contacts transfer. When
the alarm condition is corrected, the relay and all indicators reset
automatically. If latching alarms/relays are enabled the relay will need to
be reset manually, see Section 2.2.7 on page 29.
The summary alarm relay also transfers when the AT10.1 detects certain
secondary errors, indicated by meter display codes rather than a discreet
front panel red LED. Codes
E 01
through
E 13
, and
A 01
will trigger the
summary alarm. See Section 3.2 on Page 45 for all error and status codes.
Содержание AT10.1 SERIES
Страница 78: ...APPENDIX C 72 Outline AT10 1 Group II Battery Charger NEMA 1 Style 5017 Enclosure JE5025 00...
Страница 79: ...APPENDIX C 73 http www ATSeries net PDFs JE5025 00 pdf...
Страница 80: ...APPENDIX C 74 Outline AT10 1 Group II Battery Charger NEMA 1 Style 5018 Enclosure JE5026 00...
Страница 81: ...APPENDIX C 75 http www ATSeries net PDFs JE5026 00 pdf...
Страница 83: ...APPENDIX C 77 http www ATSeries net PDFs JE5028 99 pdf...
Страница 85: ...APPENDIX C 79 http www ATSeries net PDFs JE5029 99 pdf...
Страница 87: ...APPENDIX C 81 http www ATSeries net PDFs JE5030 29 pdf...
Страница 88: ...APPENDIX C 82 Schematic AT10 1 Group II Battery Charger Standard w o Options JE5032 00...
Страница 89: ...APPENDIX C 83 http www ATSeries net PDFs JE5032 00 pdf...
Страница 90: ...APPENDIX C 84 Schematic AT10 1 Group II Battery Charger w Common Options JE5032 99...
Страница 91: ...APPENDIX C 85 http www ATSeries net PDFs JE5032 99 pdf...
Страница 92: ...APPENDIX C 86 Connection Diagram AT10 1 Group II Battery Charger Standard w o Options JE5034 00...
Страница 93: ...APPENDIX C 87 http www ATSeries net PDFs JE5034 00 pdf...
Страница 94: ...APPENDIX C 88 Connection Diagram AT10 1 Group II Battery Charger w Common Options JE5034 99...
Страница 95: ...APPENDIX C 89 http www ATSeries net PDFs JE5034 99 pdf...
Страница 101: ...USER NOTES 95...