OPERATING THE AT10.1
28
Manual Equalize Method
Choose the manual equalize method when you want to equalize charge the
battery, but only when you are able to monitor the battery voltage and
gassing rate. After you select the manual equalize method, press the
CHRG MODE
key to put the AT10.1 into the equalize mode. The
EQLZ
indicator will light.
Press the
CHRG MODE
key again to return the AT10.1 to the float mode. The
FLOAT
indicator will light.
NOTICE
Never leave the AT10.1 unattended in the equalize mode
with the manual equalize method selected. A sustained
overcharge may cause permanent damage to the battery.
Auto-Equalize Timer Method
Choose the auto-equalize timer method if you have a
flooded
(non-sealed)
battery, that is subject to infrequent discharges, or when the battery will be
discharged by at least half of its rated capacity during an ac power failure.
When ac power is restored to the AT10.1, it turns on in the equalize mode
automatically, and the
EQLZ
indicator lights. At the end of the equalize
charging time that you select, the AT10.1 reverts automatically to the float
mode, and the
FLOAT
indicator lights. At any time during the equalize
charge, you can switch the AT10.1 back to float mode by pressing the
CHRG MODE
key. The
FLOAT
indicator will light.
Consult your battery manufacturer's instructions before
using the auto-equalize timer method with sealed (valve-
regulated) lead-acid batteries.
Whenever the ac supply fails for 12 seconds or longer, the auto-equalize
timer is enabled. For shorter periods, the timer behaves as listed below:
Mode before
ac failure
AC failure
duration
Mode
after
ac failure
FLOAT
less than
12 seconds
FLOAT
EQUALIZE
less than
12 seconds
Resume EQUALIZE
with time remaining
FLOAT or
EQUALIZE
12 seconds
or greater
EQUALIZE
with full time
Switching to Equalize Mode with Auto-Equalize Timer Method Selected
You can start an equalize charge at any time.
•
Press the
CHRG MODE
key. The
EQLZ
indicator will light.
When the equalize timer is finished, the AT10.1 reverts automatically to
the float mode, and the
FLOAT
indicator lights.
Содержание AT10.1 SERIES
Страница 78: ...APPENDIX C 72 Outline AT10 1 Group II Battery Charger NEMA 1 Style 5017 Enclosure JE5025 00...
Страница 79: ...APPENDIX C 73 http www ATSeries net PDFs JE5025 00 pdf...
Страница 80: ...APPENDIX C 74 Outline AT10 1 Group II Battery Charger NEMA 1 Style 5018 Enclosure JE5026 00...
Страница 81: ...APPENDIX C 75 http www ATSeries net PDFs JE5026 00 pdf...
Страница 83: ...APPENDIX C 77 http www ATSeries net PDFs JE5028 99 pdf...
Страница 85: ...APPENDIX C 79 http www ATSeries net PDFs JE5029 99 pdf...
Страница 87: ...APPENDIX C 81 http www ATSeries net PDFs JE5030 29 pdf...
Страница 88: ...APPENDIX C 82 Schematic AT10 1 Group II Battery Charger Standard w o Options JE5032 00...
Страница 89: ...APPENDIX C 83 http www ATSeries net PDFs JE5032 00 pdf...
Страница 90: ...APPENDIX C 84 Schematic AT10 1 Group II Battery Charger w Common Options JE5032 99...
Страница 91: ...APPENDIX C 85 http www ATSeries net PDFs JE5032 99 pdf...
Страница 92: ...APPENDIX C 86 Connection Diagram AT10 1 Group II Battery Charger Standard w o Options JE5034 00...
Страница 93: ...APPENDIX C 87 http www ATSeries net PDFs JE5034 00 pdf...
Страница 94: ...APPENDIX C 88 Connection Diagram AT10 1 Group II Battery Charger w Common Options JE5034 99...
Страница 95: ...APPENDIX C 89 http www ATSeries net PDFs JE5034 99 pdf...
Страница 101: ...USER NOTES 95...