NRT407 manual
Part III
Configuration
49
Parameter
number
Description
FS
16
State connected sensor on UI1: (except NRT407F901 / F902)
0=None
1=Change-over digital
2=Change-over analogue
2
17
State connected sensor on DI1:
1=Window contact
2= No function
3= Presence detector
4=Change-over sensor (NRT407F901 / F902)
1
18
State connected sensor on DI2:
1=Window contact
2=Condensation detection
3=No function
4=Change-over sensor (NRT407F901 / F902)
2
20
State connected function on UO1:
0=None
1=Thermal actuator heat
2= None
3=Heating actuator 0...10 V
4= None
5=On/off actuator heat
6= None
3
21
State connected function on UO2:
0= None
1= None
2=Thermal actuator cool
3= None
4=Cooling actuator 0…10 V
5= None
6=On/off actuator cool
4
22
State connected function on UO3:
0= None
1=Forced vent. digital
2=Analogue output (OEM)
3=None
4=Ordinary analogue output
5=None
6=Control of EC fan
1
24
Y3 output in manual mode (only if Y3 is configured as an analogue output;
not available for NRT407F902)
0 %
28
State output signal range for Y3-actuators:
0=0…10 V
1=2…10 V
2=10…2 V
3=10…0 V
0
29
State output signal range for heating actuators:
0=0…10 V
1=2…10 V
2=10…2 V
3=10…0 V
0
30
State output signal range for cooling actuators:
0=0…10 V
1=2…10 V
2=10…2 V
3=10…0 V
0
31
Period time for heating actuators with thermal actuator
60 s
32
Period time for cooling actuators with thermal actuator
60 s
33
Run time for heating actuators with increase/decrease actuators
120 s
34
Run time for cooling actuators with increase/decrease actuators
120 s
35
Neutral zone for increase/decrease actuators
2%
36
Time in hours between exercise of heating actuators
23h
37
Time in hours between exercise of cooling actuators
23h
38
Hysteresis for on/off actuators and heating
2K
39
Hysteresis for on/off actuators and cooling
2K
40
Minimum limit for the heat output
20 %
Содержание NRT407
Страница 1: ...SAUTER ITALIA SPA NRT407 ...
Страница 9: ...NRT407 manual Part I Introduction 9 Design NRT407F902 NRT407F901 ...
Страница 13: ...NRT407 manual Part I Introduction 13 ...
Страница 46: ...46 Part III Configuration NRT407 manual Chapter 13 Indications ...
Страница 54: ......
Страница 73: ...NRT407 manual Part IV Signals 73 ...
Страница 76: ...SAUTER your local partner www sauteritalia it ...