38
Part III
Configuration
NRT407 manual
Setpoint display at
setpoint adjustment
Parameter 74 is used to set what is shown in the display when the setpoint is adjusted.
0 = The added adjustment is shown in the display. Example: +1.5°C. The adjustment is
added to both the heating and cooling setpoints.
1 = The sum of the control setpoint and the adjustment is shown in the display. Example:
The control setpoint is 22°C and the added adjustment is +1.5°C. This means that the
value 23.5°C will be shown in the display. ”HEAT” or ”COOL” will flash
depending on which of the setpoint values is the control setpoint when you enter the
setpoint menu, i.e. depending on which setpoint you are changing. The adjustment is
added to both the heating and cooling setpoints.
2 = The sum of the heating setpoint and the adjustment is shown in the display. The
adjustment is added to both the heating and cooling setpoints.
3 = The sum of the cooling setpoint and the adjustment is shown in the display. The
adjustment is added to both the heating and cooling setpoints.