66
Part IV
Signals
NRT407 manual
Signal name
Type Modbus
address
Default
value
Description
RC_Setp_R.NRTStandbySetPDeadBand
R, 3
70
3°C
Neutral zone at Stand-by,
Heating sp=basic sp .heating-3 by
default,
Coolsp=Basic sp.cool+3 by default
RC_Setp_R.NRTUnOccSetPHeat
R, 3
71
15°C
Heating setpoint at Unoccupied
RC_Setp_R.NRTUnOccSetPCool
R, 3
72
30°C
Cooling setpoint at Unoccupied
RC_Setp_R.NRTFrostSetP
R, 3
73
8°C
Frost protection setpoint
RC_Setp_R.NRTSetpointOffsetPos
R, 3
74
3°C
Highest permitted setpoint
adjustment uppwards
RC_Setp_R.NRTSetpointOffsetNeg
R, 3
75
3°C
Highest permitted setpoint
adjustment downwards
RC_Setp_R.NRTSetPOffset
R, 3
76
0 °C
The setpoint adjustment
RC_Setp_R.NRTPIDPGain
R, 3
77
10°C
P-band for room controller
RC_Setp_R.NRTPIDITime
R, 3
78
300 s
I-time (s) for room controller
RC_Setp_R.NRTCVDeadband
R, 3
79
2%
Deadband for increase/decrease
actuators (%)
RC_Setp_R.NRTAIChangeOverDiffHeat
R, 3
80
3K
The difference between the
temperature in the room and the
media temperature for change over
to cooling
RC_Setp_R.NRTAIChangeOverDiffCool
R, 3
81
4K
The difference between the
temperature in the room and the
media temperature for change over
to heating
RC_Setp_R.NRTAi1Comp
R, 3
82
0°C
Temperature compensation on AI1
RC_Setp_R. NRTUi1Comp
R, 3
83
0°C
Temperature compensation on UI1
RC_Setp_R.NRTInternalTempComp
R, 3
84
0°C
Temperature compensation on
internal room sensor
RC_Setp_R.NRTTempFilterFactor
R, 3
85
0,2
Filter factor for analogue
temperature inputs
RC_Setp_R.NRTMinFlow
R, 3
86
20
Min flow at cool output when
control mode Heating/Cooling
with VAV-control is selected
Min flow at Y3 output when
control mode
Heating/Cooling/VAV is selected
RC_Setp_R.NRTMaxFlowHeat
R, 3
87
0%
Max flow on cool output when
control mode Heating/Cooling
with VAV-control is selected and
heating is applied.
RC_SetP_R.NRTRoomTempHighLimit
R, 3
88
40°C
Alarm limit for high room
temperature
RC_SetP_R.NRTRoomTempLowLimit
R, 3
89
15°C
Alarm limit for low room
temperature
Not used in this model
R, 3
90-92
-
RC_Setp_R.NRTUo3OutputManual
R, 3
93
0%
Y3 Output in manual mode
RC_Setp_R.NRTHeatOutputManual
R, 3
94
0%
Heating output in manual mode
RC_Setp_R.NRTCoolOutputManual
R, 3
95
0%
Cooling output in manual mode
RC_Setp_R.NRTRoomTempRemote
R, 3
96
-255
Room temp set by remote control
if external room sensor is
configured (-255 = disabled)
Содержание NRT407
Страница 1: ...SAUTER ITALIA SPA NRT407 ...
Страница 9: ...NRT407 manual Part I Introduction 9 Design NRT407F902 NRT407F901 ...
Страница 13: ...NRT407 manual Part I Introduction 13 ...
Страница 46: ...46 Part III Configuration NRT407 manual Chapter 13 Indications ...
Страница 54: ......
Страница 73: ...NRT407 manual Part IV Signals 73 ...
Страница 76: ...SAUTER your local partner www sauteritalia it ...