NRT407 manual
Object name
Object-ID
Description
Values
Writable
RC_Actual_X.NRTControllerState
Multistate
input, 2
Current controller state
1=Off
2=Heating
3=Cooling
No
RC_Actual_X.NRTFanSpeed
Multistate
input, 3
Current fan speed
1=Off
2=Fan speed 1
3=Fan speed 2
4=Fan speed 3
No
Multistate values
Object name
Object-ID Description
Values
Writable
RC_Setp_X.NRTHeatOutputSelect
Multistate
value, 0
Manual/Auto heat output
1=Off
2=Manual output
3=Automatic output
Yes
RC_Setp_X.NRTCoolOutputSelect
Multistate
value, 1
Manual/Auto cool output
1=Off
2=Manual output
3=Automatic output
Yes
RC_Setp_X.NRTFanSelect
Multistate
value, 2
Fan mode select
1=Off
2=Manual speed 1
3=Manual speed 2
4=Manual speed 3
5=Auto
6=Auto 2
7=Auto 1
Yes
RC_Setp_X.NRTForcedVentSelect
Multistate
value, 3
Manual/Auto forced
ventilation
1=Off
2=Manual On
3=Auto
Yes
RC_Setp_X.NRTChangeOverSelect Multistate
value, 4
Manual/Auto change-over 1=Heating
2=Cooling
3=Auto
Yes
RC_Setp_X.NRTRemoteState
Multistate
value, 5
Remote control unit state
1=Off
2=Unoccupied
3=Stand-by
4=Occupied
6=No remote control
Yes
Device
The device object contains two writable properties; Description and Location. Description
can be 17 characters long, and Location can be 33 characters long, if using single byte
character encoding.
Содержание NRT407
Страница 1: ...SAUTER ITALIA SPA NRT407 ...
Страница 9: ...NRT407 manual Part I Introduction 9 Design NRT407F902 NRT407F901 ...
Страница 13: ...NRT407 manual Part I Introduction 13 ...
Страница 46: ...46 Part III Configuration NRT407 manual Chapter 13 Indications ...
Страница 54: ......
Страница 73: ...NRT407 manual Part IV Signals 73 ...
Страница 76: ...SAUTER your local partner www sauteritalia it ...