NRT407 manual
Part IV
Signals
71
Binary values
Object name
Object-ID
Description
Values
Writable
RC_Actual_L.NRTForcedVentilation
Binary
value, 0
Indicate forced ventilation
ON/OFF
No
RC_Actual_L.NRTCVHeatPulsProp
Binary
value, 1
Indicate pulse prop heating
ACTIVE/
INACTIVE
No
RC_Actual_L.NRTCVCoolPulsProp
Binary
value, 2
Indicate pulse prop cooling
ACTIVE/
INACTIVE
No
RC_Actual_L.NRTCVHeatInc
Binary
value, 3
Indicate increase heating
ACTIVE/
INACTIVE
No
RC_Actual_L.NRTCVHeatDec
Binary
value, 4
Indicate decrease heating
ACTIVE/
INACTIVE
No
RC_Actual_L.NRTCVCoolInc
Binary
value, 5
Indicate increase cooling
ACTIVE/
INACTIVE
No
RC_Actual_L.NRTCVCoolDec
Binary
value, 6
Indicate decrease cooling
ACTIVE/
INACTIVE
No
RC_Actual_L.NRTChangeOverState
Binary
value, 7
Indicate change over state from
both digital and analogue input
ACTIVE/
INACTIVE
No
RC_Actual_L.NRTRoomTempSensorAlarm
Binary
value, 8
Indicate sensor alarm on room
sensor
ACTIVE/
INACTIVE
No
RC_Setp_L.NRTBypass
Binary
value, 9
Force the unit in Bypass mode.
Is automatically returned after
Bypass time (default=120 min)
ACTIVE/
INACTIVE
Yes
RC_Setp _L.NRTShutDown
Binary
value, 10
Force the unit in ShutDown
state
ACTIVE/
INACTIVE
Yes
All binary values have normal polarity.
Loop
Object name
Object-ID
Description
Regulator
Loop, 0
The NRT Regulator
Multistate inputs
Object name
Object-ID
Description
Values
Writable
RC_Actual_X.NRTFanSwitch
Multistate
input, 0
Fan switch state
1=OFF
2=LOW
3=MEDIUM
4=HIGH
5=AUTO
No
RC_Actual_X.NRTUnitState
Multistate
input, 1
Current unit state
1=Off
2=Unoccupied
3=Stand-by
4=Occupied
5=Bypass
No
Содержание NRT407
Страница 1: ...SAUTER ITALIA SPA NRT407 ...
Страница 9: ...NRT407 manual Part I Introduction 9 Design NRT407F902 NRT407F901 ...
Страница 13: ...NRT407 manual Part I Introduction 13 ...
Страница 46: ...46 Part III Configuration NRT407 manual Chapter 13 Indications ...
Страница 54: ......
Страница 73: ...NRT407 manual Part IV Signals 73 ...
Страница 76: ...SAUTER your local partner www sauteritalia it ...