For handling of the Occupancy button in combination with central control, please see the
section entitled
Central control
, below.
Occupancy detector
For local control of the operating mode between the preset operating mode and Bypass, an
occupancy detector is connected.
When occupancy is indicated, the controller changes operating mode to Bypass. If you want
to be able to enter the room temporarily without activating Presence (to, for example, pick
something up) it is possible to configure a power-up delay. This means that Presence is not
activated until the power-up delay has expired. The Presence delay can be set to a value
between 0 and 60 minutes (FS=0 min).
In Bypass on presence, there is a switch-off timer, which means that if there is no occupancy
indication during this time (FS=10 min), the controller will return to the preset operating
mode.