NRT407 manual
Part IV
Signals
59
Coil status register
Signal name
Type
Modbus
address
Default
value
Description
RC_Setp_L.NRTBypass
L,1
1
0
Force the unit in Bypass mode. Is
automatically returned after Bypass
time.
0=No bypass
1=Bypass
RC_Setp_L.NRTShutDown
L,1
2
0
Force the unit in Shutdown state.
0=No Shutdown
1=Shutdown
RC_Setp_L.NRTNotUsed
L,1
3
Not used
RC_Setp_L.NRTDiNC(0)
L,1
4
Not used
RC_Setp_L.NRTDi1NC
L,1
5
0
State NO/NC digital input 1:
0=NO (Normally open)
1=NC (Normally closed)
RC_Setp_L.NRTDi2NC
L,1
6
1
State NO/NC digital input 2:
0=NO (Normally open)
1=NC (Normally closed)
RC_Setp_L.NRTUDi1NC
L,1
7
0
State NO/NC universal input 1:
0=NO (Normally open)
1=NC (Normally closed)
RC_Setp_L.NRTCVHeatPulsPropNC
L,1
8
0
Selection of heating output function
(NO/NC):
0=NO (Normally open)
1=NC (Normally closed)
Not used in this model
L,1
9-13
0
RC_Setp_L.NRTMinFanSpeed
L,1
14
0
The fan will never stop:
0=Off
1=On
RC_Setp_L.NRTCVCoolPulsPropNC L,1
15
0
Selection of cooling output functions
(NO/NC):
0=NO (Normally open)
1=NC (Normally closed)
RC_Setp_L.NRTComFactoryDefault
L,1
16
0
Resets communication to default
values:
1=Reset (returns to 0)
Input register
Signal name
Type
Modbus address
Description
RC_Actual_X.NRTSoftware
X, 4
1
Model
RC_Actual_X.NRTVerMajor
X, 4
2
Version Major
RC_Actual_X.NRTVerMinor
X, 4
3
Version Minor
RC_Actual_X.NRTVerBranch
X, 4
4
Version Branch
RC_Actual_X.NRTRevision
X, 4
5
Revision
Содержание NRT407
Страница 1: ...SAUTER ITALIA SPA NRT407 ...
Страница 9: ...NRT407 manual Part I Introduction 9 Design NRT407F902 NRT407F901 ...
Страница 13: ...NRT407 manual Part I Introduction 13 ...
Страница 46: ...46 Part III Configuration NRT407 manual Chapter 13 Indications ...
Страница 54: ......
Страница 73: ...NRT407 manual Part IV Signals 73 ...
Страница 76: ...SAUTER your local partner www sauteritalia it ...