18
Part II
Installation
NRT407 manual
The communication cable must be a screened twisted pair cable. The shield must be
connected to G0 on one (and only one) NRT controller in each separate power supply loop
with 24 V AC. If the length of the loop exceeds 300 m, a repeater is required. See figure 6.
Figure 6.
The figure below shows the location of the terminals. The connection diagrams and tables on
the following pages show the wiring for basic models and models for fan control.
Figure 7. Bottom plate with terminals