Alarm Details
(1-2) [Alarm “P29”]
No
Start of defect diagnosis
Is the power voltage correct?
Improve the power voltage line.
Yes
No
Repair the wiring connectors.
Check the following wiring:
Display on PCB
HIC PCB side
Outdoor unit
control PCB side
HIC+
CN04
CN069 (wire : yellow)
HIC-
CN05
CN070 (wire : gray)
HIC1
CN01
CN207 (10P white)
HIC2
CN02
CN206 (8P white)
RE1 (Reactor)
-
CN066 (wire : white)
RE2 (Reactor)
-
CN067 (wire : white)
DC+ (Bridge Diode)
-
CN062 (wire : red)
DC- (Bridge Diode)
-
CN063 (wire : blue)
Are the wiring connector
connections OK?
Repair the wiring connectors.
HIC PCB side
U (CN06) pink
V (CN07) white
W (CN08) blue
No (The CT detected value is abnormal.)
Replace the outdoor unit control PCB.
When the CT detected value is abnormal, the alarm occurs and the compressor stops
after 1-minute operation.
Verify the CT current values by performing the following steps.
Confi rm that the difference between CT current detected values (*) and the current value
(measured by clamp meter) of power source wiring (between outdoor unit power terminal
and control PCB; red, white, blue) is within 1A.
* Verifi cation method of CT current detect
1. With the outdoor unit maintenance remote controller
Check with the code "14" of the temperature sensor display function.
2. With the indoor unit remote controller
Check with the sensor address "14" of the temperature sensor display function.
No (Abnormal resistance value)
Replace the HIC PCB.
• Verifi cation method: Remove the HIC PCB and measure the resistance at all areas.
Refer to the page 5 - 12.
Replace the HIC PCB if the readings are below permissible values.
No (Defective insulation)
Replace the compressor. • Potential cause:
Insulation failure caused by the compressor lock.
• Verification Method
Remove the wires from the connectors on the top of the compressor.
Measure the insulation resistance of the U, V and W phases and
confirm that they are 1M Ω or more.
No
Replace C1, TS sensor.
Replace electronic expansion valve.
Replace the outdoor unit control PCB and HIC PCB.
No
Are the U/V/W
connections on the HIC
PCB and compressor
terminal OK?
Is the detected
values of CT current
(current values) during
compressor operation
normal?
Are the resistance
values permissible at all
areas in HIC PCB?
Is the insulation on the
compression OK?
Is electronic
expansion valve operation
normal?
Is C1, TS sensor normal?
Yes
Yes
Yes
Yes
Yes
Yes
Yes
(No problem
with the CT
detected value)
(No problem with the resistance value)
(No problem with the insulation)
No
Start-up failure of the compressor (will not start up)
Related parts
• HIC PCB (CR-HIC160B-E, HIC-CR364GVH8, HIC-CR604GVH8)
• Outdoor unit control PCB (CR-C486VH, CR256VH8, CR606VH8)
Check the following:
Check to ascertain that the power voltage is within the permissible range of 198 to 264V
for indoor and outdoor units regardless of whether the compressor is operating or not.
Regarding 3-phase outdoor unit, the power voltage is 342 to 456 V.
* Pay special attention to whether the voltage drops after compressor operations while measuring.
SM830160-03̲Classic̲PAC-i̲A4.ind9 9
SM830160-03̲Classic̲PAC-i̲A4.ind9 9
2010/02/16 10:30:05
2010/02/16 10:30:05
Содержание SPW-C256VH
Страница 364: ... MEMO 1 358 ...
Страница 398: ... MEMO 2 34 ...
Страница 402: ...3 4 3 3 1 Indoor Units 4 Way Air Discharge Semi Concealed Type SPW XM125 165 185H Electric Wiring Diagram 䡵 ...
Страница 403: ...3 5 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Electric Wiring Diagram 䡵 ...
Страница 404: ...3 6 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Schematic Diagram 䡵 ...
Страница 405: ...3 7 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Electric Wiring Diagram 䡵 ...
Страница 406: ...3 8 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Schematic Diagram 䡵 ...
Страница 409: ...3 11 3 3 1 Indoor Units Concealed Duct Type SPW UR124 164 184 254 364 484 604GH56 A B Electric Wiring Diagram 䡵 ...
Страница 410: ...3 12 3 3 1 Indoor Units Concealed Duct Type SPW UR124 164 184 254 364 484 604GH56 A B Schematic Diagram 䡵 ...
Страница 411: ...3 13 3 3 1 Indoor Units Concealed Duct Type SPW U125 165 185 255 365 485 605H Electric Wiring Diagram 䡵 ...
Страница 412: ...3 14 3 3 1 Indoor Units Concealed Duct Type SPW U125 165 185 255 365 485 605H Schematic Diagram 䡵 ...
Страница 415: ...3 17 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Electric Wiring Diagram 䡵 ...
Страница 416: ...3 18 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Schematic Diagram 䡵 ...
Страница 417: ...3 19 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256VH ...
Страница 419: ...3 21 3 3 2 Outdoor Units Electric Wiring Diagram SPW C366VH ...
Страница 421: ...3 23 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486VH ...
Страница 423: ...3 25 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256 366VH8 ...
Страница 425: ...3 27 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486 606VH8 ...
Страница 472: ... MEMO 6 10 ...
Страница 490: ... MEMO 7 18 ...
Страница 517: ...SANYO Electric Co Ltd Printed in Japan 201002E DC ...