2-2
2-1. Preparing for Test Run
Before attempting to start the air conditioner,
check the following:
(1) All loose matter is removed from the cabinet
especially steel filings, bits of wire, and clips.
(2) The control wiring is correctly connected and all
electrical connections are tight.
(3) The protective spacers for the compressor used
for transportation have been removed. If not,
remove them now.
(4) The transportation pads for the indoor fan have
been removed. If not, remove them now.
(5) The power has been supplied to the unit for at
least 5 hours before starting the compressor. The
bottom of the compressor should be warm to the
touch and the crankcase heater around the feet of
the compressor should be hot to the touch. (Fig.
2-1)
(6) Both the gas and liquid tube service valves are open. If
not, open them now. (Fig. 2-2).
ON
(Power must be turned ON at least
5 hours before attempting test run)
Power mains switch
Fig. 2-1
Fig. 2-2
Liquid tube
Gas tube
(7) Request that the customer be present for the test
run. Explain the contents of the instruction manual,
and then have the customer actually operate the
system.
(8) Be sure to give the instruction manual and
warranty certificate to the customer.
(9) When replacing the control PCB, be sure to make
all the same settings on the new PCB as were in
use before replacement.
The existing EEPROM is not changed, and is
connected to the new control PCB.
X, XM, T, U, US Types
2-2. Caution
This unit may be used in a single-type
refrigerant system where 1 outdoor unit is
connected to 1 indoor unit, and also in a system
where 1 outdoor unit is connected to multiple
indoor units (maximum 4).
* If multiple indoor units are used, also refer to “2-8.
System Control”.
The indoor and outdoor unit control PCB utilizes
a semiconductor memory element (EEPROM).
The settings required for operation were made
at the time of shipment.
Only the correct combinations of indoor and
outdoor units can be used.
This test run section describes primarily
the procedure when using the wired remote
controller.
2-3. Test Run Procedure
Fig. 2-3
Recheck the items to check
before the test run.
(See 2-4)
Check the combination (wiring) of
indoor and outdoor units.
Is system “single-type”?
(1 indoor unit is connected
to 1 outdoor unit and remote
controller)
Is group control with
multiple outdoor units used?
Set the outdoor
unit system
address.
(See 2-8-1 to 5)
YES
NO
NO
YES
(See 2-8-3)
Setting the Outdoor
Unit System
Address
(Automatic
Address setting)
Turn ON the
indoor and
outdoor power.
Turn ON the indoor and
outdoor power.
(See 2-8-4)
Automatic Address
Setting
Use the remote
controller to
perform automatic
address setting.
Indicate (mark) the
combination number.
Set the remote controller to
“test run”.
Can
operation be
started?
Refer to “Table of Self-
Diagnostic Functions”
to check the system.
In addition, refer to
2-8-1 to 5 and correct
any items that need to
be corrected.
(*1)
Automatic
Address
setting
(See 2-8-5)
(See 2-5)
YES
Return the remote controller
to normal control.
Note: Check the indoor-side
drainage.
(*1) Required for simultaneous-
operation multi systems and for
group control.
NO
SM830160-03̲Classic̲PAC-i̲A4.ind2 2
SM830160-03̲Classic̲PAC-i̲A4.ind2 2
2010/02/16 10:28:07
2010/02/16 10:28:07
Содержание SPW-C256VH
Страница 364: ... MEMO 1 358 ...
Страница 398: ... MEMO 2 34 ...
Страница 402: ...3 4 3 3 1 Indoor Units 4 Way Air Discharge Semi Concealed Type SPW XM125 165 185H Electric Wiring Diagram 䡵 ...
Страница 403: ...3 5 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Electric Wiring Diagram 䡵 ...
Страница 404: ...3 6 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Schematic Diagram 䡵 ...
Страница 405: ...3 7 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Electric Wiring Diagram 䡵 ...
Страница 406: ...3 8 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Schematic Diagram 䡵 ...
Страница 409: ...3 11 3 3 1 Indoor Units Concealed Duct Type SPW UR124 164 184 254 364 484 604GH56 A B Electric Wiring Diagram 䡵 ...
Страница 410: ...3 12 3 3 1 Indoor Units Concealed Duct Type SPW UR124 164 184 254 364 484 604GH56 A B Schematic Diagram 䡵 ...
Страница 411: ...3 13 3 3 1 Indoor Units Concealed Duct Type SPW U125 165 185 255 365 485 605H Electric Wiring Diagram 䡵 ...
Страница 412: ...3 14 3 3 1 Indoor Units Concealed Duct Type SPW U125 165 185 255 365 485 605H Schematic Diagram 䡵 ...
Страница 415: ...3 17 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Electric Wiring Diagram 䡵 ...
Страница 416: ...3 18 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Schematic Diagram 䡵 ...
Страница 417: ...3 19 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256VH ...
Страница 419: ...3 21 3 3 2 Outdoor Units Electric Wiring Diagram SPW C366VH ...
Страница 421: ...3 23 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486VH ...
Страница 423: ...3 25 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256 366VH8 ...
Страница 425: ...3 27 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486 606VH8 ...
Страница 472: ... MEMO 6 10 ...
Страница 490: ... MEMO 7 18 ...
Страница 517: ...SANYO Electric Co Ltd Printed in Japan 201002E DC ...