7
Item code
Item
Description
1F
(Upper limit)
20
(Lower limit)
Change to the
remote control
temperature
setting range
Cooling
This setting changes the temperature range (upper limit and lower
limit) which is set from the remote controller or central control
device.
The set upper limit must be greater than or equal to the lower limit.
If the temperature setting is to be a single point, set the upper limit
and lower limit to the same temperature.
21
(Upper limit)
22
(Lower limit)
Heating
23
(Upper limit)
24
(Lower limit)
Drying
25
(Upper limit)
26
(Lower limit)
Auto
heat/cool
29
Humidifier operation which
ignores the heat exchanger
temperature
During heating operation, the humidifier operates when the heat
exchanger temperature is suitable for humidifying. This setting is
used to ignore this condition for humidifier operation and operate the
humidifier more.
2A
Filter input switching
This setting switches the filter input according to the purpose of use.
2C
Indoor unit electronic
control valve
This setting indicates whether or not an indoor unit electronic control
valve is present.
At the time of shipping, this setting is set according to the conditions
of the indoor unit.
2E
T10 terminal input
switching
Ordinarily, the T10 terminal is used as the HA terminal at the time
of shipping. However, this setting is used when the T10 terminal is
used for OFF reminder or for fire prevention input.
31
Ventilation fan operation
from remote controller
It is possible to install a total heat exchanger and ventilation fan in
the system, which can be started and stopped by the wired remote
controller. The ventilation fan can operate linked with the start and
stop of the indoor unit, or can be operated even when the indoor unit
is stopped.
Use a ventilation fan that can accept the no-voltage A contact as the
external input signal.
In the case of group control, the fans are operated together. They
cannot be operated individually.
32
Switching to remote
controller sensor
This setting is used to switch from the body sensor to the remote
controller sensor.
Check that “remote controller sensor” is displayed.
Do not use this setting with models that do not include a remote
controller sensor.
Do not use this setting if both the body sensor and remote sensor
are used.
34
ON/OFF of “Operation
change control in progress”
display
In a MULTI system with multiple remote controllers, switching
between heating and cooling is restricted, and “Operation change
control in progress” is displayed.
This setting is used to prevent this display from appearing.
Refer to the item concerned with operating mode priorities.
35
OFF reminder function for
weekly timer
This setting switches the operation when the weekly timer is
connected to the remote controller.
This can be used to prevent cases in which the unit is accidentally
left ON. There is no change when this setting is ON, however it is
necessary to set the weekly timer ON time.
(Continued)
7-13
SM830160-03̲Classic̲PAC-i̲A4.ind13 13
SM830160-03̲Classic̲PAC-i̲A4.ind13 13
2010/02/16 10:30:51
2010/02/16 10:30:51
Содержание SPW-C256VH
Страница 364: ... MEMO 1 358 ...
Страница 398: ... MEMO 2 34 ...
Страница 402: ...3 4 3 3 1 Indoor Units 4 Way Air Discharge Semi Concealed Type SPW XM125 165 185H Electric Wiring Diagram 䡵 ...
Страница 403: ...3 5 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Electric Wiring Diagram 䡵 ...
Страница 404: ...3 6 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Schematic Diagram 䡵 ...
Страница 405: ...3 7 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Electric Wiring Diagram 䡵 ...
Страница 406: ...3 8 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Schematic Diagram 䡵 ...
Страница 409: ...3 11 3 3 1 Indoor Units Concealed Duct Type SPW UR124 164 184 254 364 484 604GH56 A B Electric Wiring Diagram 䡵 ...
Страница 410: ...3 12 3 3 1 Indoor Units Concealed Duct Type SPW UR124 164 184 254 364 484 604GH56 A B Schematic Diagram 䡵 ...
Страница 411: ...3 13 3 3 1 Indoor Units Concealed Duct Type SPW U125 165 185 255 365 485 605H Electric Wiring Diagram 䡵 ...
Страница 412: ...3 14 3 3 1 Indoor Units Concealed Duct Type SPW U125 165 185 255 365 485 605H Schematic Diagram 䡵 ...
Страница 415: ...3 17 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Electric Wiring Diagram 䡵 ...
Страница 416: ...3 18 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Schematic Diagram 䡵 ...
Страница 417: ...3 19 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256VH ...
Страница 419: ...3 21 3 3 2 Outdoor Units Electric Wiring Diagram SPW C366VH ...
Страница 421: ...3 23 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486VH ...
Страница 423: ...3 25 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256 366VH8 ...
Страница 425: ...3 27 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486 606VH8 ...
Страница 472: ... MEMO 6 10 ...
Страница 490: ... MEMO 7 18 ...
Страница 517: ...SANYO Electric Co Ltd Printed in Japan 201002E DC ...