7
When the operating mode at the priority remote controller is changed, the operating modes of other remote
controllers change as shown below.
Mode change at priority remote controller Operating modes at other remote controllers
Current mode
New mode
Current mode
New mode
Cooling or dry
Heating
Cooling or dry
Heating
Fan
Fan (not changed)
Heating
Cooling
Heating
Cooling
Fan
Fan (not changed)
Cooling
Dry
Cooling
Cooling (not changed)
Dry
Dry (not changed)
Heating
Dry
Heating
Cooling
Fan
Fan (not changed)
Cooling or dry
Fan
Cooling
Cooling (not changed)
Dry
Dry (not changed)
Fan
Fan (not changed)
Heating
Fan
Heating
Heating (not changed)
Fan
Fan (not changed)
Item code
Item
Description
05
Fan speed setting when
heating thermostat is OFF
Changes the fan speed setting when the heating thermostat is OFF.
06
Heating intake
temperature shift
Shifts the intake temperature during heating.
Can be set when the body thermostat is used.
07
Electric heater installation
Set when cost distribution is performed using an AMY central control
system or similar system, and when an optional electric heater is installed.
(This is unrelated to control of the electric heater.)
08
Humidifying when heater
thermostat is OFF
Normally humidifying does not occur when the thermostat is OFF during
heating operation. However, this setting can be changed in order to
increase the amount of humidifying.
Caution: In order to avoid water leakage and damage to the fan, do not
use this setting unless a vaporizing humidifier is used.
0D
Permit/prohibit automatic
heating/cooling
This setting can be used to prevent the automatic heating/cooling display
on the remote control if the unit configuration permits automatic heating/
cooling operation.
0F
Cooling-only
This setting allows a heat pump indoor unit to be operated as a cooling-
only unit.
7-11
SM830160-03̲Classic̲PAC-i̲A4.ind11 11
SM830160-03̲Classic̲PAC-i̲A4.ind11 11
2010/02/16 10:30:51
2010/02/16 10:30:51
Содержание SPW-C256VH
Страница 364: ... MEMO 1 358 ...
Страница 398: ... MEMO 2 34 ...
Страница 402: ...3 4 3 3 1 Indoor Units 4 Way Air Discharge Semi Concealed Type SPW XM125 165 185H Electric Wiring Diagram 䡵 ...
Страница 403: ...3 5 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Electric Wiring Diagram 䡵 ...
Страница 404: ...3 6 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Schematic Diagram 䡵 ...
Страница 405: ...3 7 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Electric Wiring Diagram 䡵 ...
Страница 406: ...3 8 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Schematic Diagram 䡵 ...
Страница 409: ...3 11 3 3 1 Indoor Units Concealed Duct Type SPW UR124 164 184 254 364 484 604GH56 A B Electric Wiring Diagram 䡵 ...
Страница 410: ...3 12 3 3 1 Indoor Units Concealed Duct Type SPW UR124 164 184 254 364 484 604GH56 A B Schematic Diagram 䡵 ...
Страница 411: ...3 13 3 3 1 Indoor Units Concealed Duct Type SPW U125 165 185 255 365 485 605H Electric Wiring Diagram 䡵 ...
Страница 412: ...3 14 3 3 1 Indoor Units Concealed Duct Type SPW U125 165 185 255 365 485 605H Schematic Diagram 䡵 ...
Страница 415: ...3 17 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Electric Wiring Diagram 䡵 ...
Страница 416: ...3 18 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Schematic Diagram 䡵 ...
Страница 417: ...3 19 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256VH ...
Страница 419: ...3 21 3 3 2 Outdoor Units Electric Wiring Diagram SPW C366VH ...
Страница 421: ...3 23 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486VH ...
Страница 423: ...3 25 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256 366VH8 ...
Страница 425: ...3 27 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486 606VH8 ...
Страница 472: ... MEMO 6 10 ...
Страница 490: ... MEMO 7 18 ...
Страница 517: ...SANYO Electric Co Ltd Printed in Japan 201002E DC ...