2
2-28
2-28. Test Run Procedure
2-29. Items to Check Before the Test Run
(1) Turn the remote power switch ON at least 12 hours in advance in order to energize the crank case heater.
(2) Fully open the closed valves on the liquid-tube and gas-tube sides.
2-30. Test Run Using the Remote Controller
(1) Press and hold the remote controller
button for 4 seconds or longer. Then press the
button.
“TEST” appears in the LCD display during the test run.
Temperature control is not possible when test run mode is engaged.
(This mode places a large load on the devices. Use it only when performing the test run.)
(2) Use either Heating or Cooling mode to perform the test run.
NOTE
The outdoor unit will not operate for approximately 3 minutes after the power is turned ON or after it stops
operating.
(3) If normal operation is not possible, a code appears on the remote controller LCD display.
Refer to “Table of Self-Diagnostic Functions and Corrections” on the next page, and correct the problem.
(4) After the test run is completed, press the
button again. Check that “TEST” disappears from the LCD display.
(This remote controller includes a function that cancels test run mode after a 60-minute timer has elapsed, in
order to prevent continuous test run operation.)
(5) For the test run of an inverter outdoor unit, operate the compressors for a minimum of 10 minutes (in order to
check for open phase).
*
When performing a test run using a wired remote controller, operation is possible without attaching the
cassette-type ceiling panel.( “P09” will not be displayed.)
Fig. 2-28
Recheck the items to check befor the test run.
(See 2-29)
(See 2-32-1)
Check the combination (wiring) of
indoor and outdoor units.
YES
NO
YES
Is system “single-type”?
Is group
control with multiple
outdoor units
used?
NO
Set the outdoor unit system address.
(See 2-32-2) How to Set the Outdoor Unit System Address
Set the automatic address setting
from outdoor unit or remote controller.
(See 2-32-1) How to Set Automatic Address
(*) Indicate (mark) the combination number. (See 2-32-3, -4)
Turn ON the indoor and outdoor power. (Automatic Address setting)
Turn ON the indoor and
outdoor power.
(*) Required for simultaneous operation multi systems and
for group control.
Set the remote controller to “test run”.
Return the remote controller to normal control.
Can
operation be
started?
(Automatic Address setting)
(See 2-30)
(See 2-31)
NO
YES
Note: Check the indoor-side drainage.
Refer to “Table of Self-Diagnostic
Functions” to check the system.
In addition, refer to 2-32 and correct any
items that need to be corrected.
SM830160-03̲Classic̲PAC-i̲A4.ind28 28
SM830160-03̲Classic̲PAC-i̲A4.ind28 28
2010/02/16 10:28:15
2010/02/16 10:28:15
Содержание SPW-C256VH
Страница 364: ... MEMO 1 358 ...
Страница 398: ... MEMO 2 34 ...
Страница 402: ...3 4 3 3 1 Indoor Units 4 Way Air Discharge Semi Concealed Type SPW XM125 165 185H Electric Wiring Diagram 䡵 ...
Страница 403: ...3 5 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Electric Wiring Diagram 䡵 ...
Страница 404: ...3 6 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Schematic Diagram 䡵 ...
Страница 405: ...3 7 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Electric Wiring Diagram 䡵 ...
Страница 406: ...3 8 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Schematic Diagram 䡵 ...
Страница 409: ...3 11 3 3 1 Indoor Units Concealed Duct Type SPW UR124 164 184 254 364 484 604GH56 A B Electric Wiring Diagram 䡵 ...
Страница 410: ...3 12 3 3 1 Indoor Units Concealed Duct Type SPW UR124 164 184 254 364 484 604GH56 A B Schematic Diagram 䡵 ...
Страница 411: ...3 13 3 3 1 Indoor Units Concealed Duct Type SPW U125 165 185 255 365 485 605H Electric Wiring Diagram 䡵 ...
Страница 412: ...3 14 3 3 1 Indoor Units Concealed Duct Type SPW U125 165 185 255 365 485 605H Schematic Diagram 䡵 ...
Страница 415: ...3 17 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Electric Wiring Diagram 䡵 ...
Страница 416: ...3 18 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Schematic Diagram 䡵 ...
Страница 417: ...3 19 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256VH ...
Страница 419: ...3 21 3 3 2 Outdoor Units Electric Wiring Diagram SPW C366VH ...
Страница 421: ...3 23 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486VH ...
Страница 423: ...3 25 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256 366VH8 ...
Страница 425: ...3 27 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486 606VH8 ...
Страница 472: ... MEMO 6 10 ...
Страница 490: ... MEMO 7 18 ...
Страница 517: ...SANYO Electric Co Ltd Printed in Japan 201002E DC ...