Selecting the Installation Site
Indoor Unit
CAUTION
When moving the unit during or after unpacking,
make sure to lift it by holding its lifting lugs. Do
not exert any pressure on other parts, especially
the refrigerant piping, drain piping and fl ange
parts.
If you think the humidity inside the ceiling
might exceed 30°C and RH 80%, reinforce the
insulation on the unit body. Use glass wool or
polyethylene foam as insulation so that it is no
thicker than 10 mm and fi ts inside the ceiling
opening.
AVOID:
areas where leakage of fl ammable gas may be
expected.
places where large amounts of oil mist exist.
direct sunlight.
locations near heat sources which may affect the
performance of the unit.
locations where external air may enter the room
directly. This may cause “condensation” on the
air discharge ports, causing them to spray or drip
water.
locations where the remote controller will be
splashed with water or affected by dampness or
humidity.
installing the remote controller behind curtains or
furniture.
locations where high-frequency emissions are
generated.
places where blocks air passages.
places where the false ceiling is not noticeably on
an incline.
DO:
select an appropriate position from which every
corner of the room can be uniformly cooled.
select a location where the ceiling is strong enough
to support the weight of the unit.
select a location where tubing and drain pipe have
the shortest run to the outdoor unit.
allow room for operation and maintenance as well
as unrestricted air fl ow around the unit.
install the unit within the maximum elevation
difference above or below the outdoor unit and
within a total tubing length (L) from the outdoor unit
as detailed in Tables 1-1 and 1-2.
allow room for mounting the remote controller
about 1m off the fl oor, in an area that is not in direct
sunlight or in the fl ow of cool air from the indoor
unit.
places where optimum air distribution can be
ensured.
places where suffi cient clearance for maintenance
and service can be ensured.
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Fig. 1-1
1 m
1 m
1 m
1 m
1 m
25 cm
25 cm
25 cm
Fig. 1-2
Fig. 1-3
NOTE
Ceiling-Mounted Type
Ceiling
min. 25 cm
or more
Front view
Wall
The rear of the indoor unit can be installed fl ush
against the wall.
Air
discharge
min. 50 cm
Air intake
Max. 25 cm
Obstacle
Side view
min. 25 cm
or more
Concealed-Duct Type
4-Way Semi-Concealed Type
Wall-Mounted Type
min.
15 cm
Front view
min. 15 cm min.
15 cm
SM830160-03̲Classic̲PAC-i̲A4.ind327 327
SM830160-03̲Classic̲PAC-i̲A4.ind327 327
2010/02/16 10:26:50
2010/02/16 10:26:50
Содержание SPW-C256VH
Страница 364: ... MEMO 1 358 ...
Страница 398: ... MEMO 2 34 ...
Страница 402: ...3 4 3 3 1 Indoor Units 4 Way Air Discharge Semi Concealed Type SPW XM125 165 185H Electric Wiring Diagram 䡵 ...
Страница 403: ...3 5 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Electric Wiring Diagram 䡵 ...
Страница 404: ...3 6 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Schematic Diagram 䡵 ...
Страница 405: ...3 7 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Electric Wiring Diagram 䡵 ...
Страница 406: ...3 8 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Schematic Diagram 䡵 ...
Страница 409: ...3 11 3 3 1 Indoor Units Concealed Duct Type SPW UR124 164 184 254 364 484 604GH56 A B Electric Wiring Diagram 䡵 ...
Страница 410: ...3 12 3 3 1 Indoor Units Concealed Duct Type SPW UR124 164 184 254 364 484 604GH56 A B Schematic Diagram 䡵 ...
Страница 411: ...3 13 3 3 1 Indoor Units Concealed Duct Type SPW U125 165 185 255 365 485 605H Electric Wiring Diagram 䡵 ...
Страница 412: ...3 14 3 3 1 Indoor Units Concealed Duct Type SPW U125 165 185 255 365 485 605H Schematic Diagram 䡵 ...
Страница 415: ...3 17 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Electric Wiring Diagram 䡵 ...
Страница 416: ...3 18 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Schematic Diagram 䡵 ...
Страница 417: ...3 19 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256VH ...
Страница 419: ...3 21 3 3 2 Outdoor Units Electric Wiring Diagram SPW C366VH ...
Страница 421: ...3 23 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486VH ...
Страница 423: ...3 25 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256 366VH8 ...
Страница 425: ...3 27 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486 606VH8 ...
Страница 472: ... MEMO 6 10 ...
Страница 490: ... MEMO 7 18 ...
Страница 517: ...SANYO Electric Co Ltd Printed in Japan 201002E DC ...