2-7. Table of Self-Diagnostic Functions and Corrections (X, XM, T, U, US Types)
Wired remote
controller
display
Indoor unit
receiver lamp
Cause
Correction
1:1 connection (single type)
Group connection
Simultaneous-operation multi system
(fl
exible
combination)
Control by main-sub
remote controllers
Nothing is
displayed
Nothing is
displayed.
•
Remote controller is not connected
correctly.
• Indoor unit power is not ON.
•
Remote controller is not connected
with indoor unit correctly.
• Indoor unit power is not ON.
• Same at left
• Same at left
Connect the remote controller
correctly.
Turn ON the indoor unit power.
E01
displayed
Operating lamp is
blinking.
•
Automatic address setting has not
been completed.
•
Inter-unit control wiring is cut or is not
connected correctly.
•
Remote controller is not connected
correctly (remote controller receiving
failure).
•
Automatic address setting has not
been completed.
•
Inter-unit control wiring is cut or is
not connected correctly.
•
Remote controller is not connected
with indoor unit correctly.
• Same at left
• Same at left
Check the remote controller and inter-
unit control wiring.
Perform automatic address setting
(See 2-8-4).
E02
displayed
•
Remote controller is not connected
correctly (failure in transmission from
remote controller to indoor unit).
•
Remote controller is not connected
with indoor unit correctly.
• Same at left
• Same at left
Connect the remote controller
correctly
E09
displayed
-—
—
—
•
2 remote
controllers are
set as the main
remote controller.
Refer to 2-8-6 Main-sub remote
Control, and make the correct
settings.
E14
displayed
—
—
•
Remote controller communication
wiring is cut or is not connected
correctly.
• Same at left
Check the remote controller
communication wiring.
Perform automatic address setting
again.
E04
displayed
Standby lamp is
blinking.
•
Indoor-outdoor inter-unit wiring is not
connected correctly.
• Same at left
• Same at left
• Same at left
Connect the wiring correctly.
E06
displayed
•
Indoor-outdoor inter-unit wiring is
cut or is not connected correctly.
• Same at left
• Same at left
Refer to 2-8 System Control, and
make the correct settings.
E15
displayed
• Indoor unit capacity is too low.
• Same at left
• Same at left
• Same at left
Check that the total capacities of
the indoor and outdoor units are
appropriate.
E16
displayed
• Indoor unit capacity is too high
E20
displayed
•
No serial signal is being received at all
from the indoor units.
Check that the indoor unit power is
ON, and that the inter-unit control
wiring is connected correctly.
P05
displayed
Operation lamp
and Standby
lamp are blinking
alternately.
•
Reversed phase in the outdoor unit
single-phase or open phase in the
outdoor unit 3-phase power.
• Insuffi
cient gas
•
Reversed phase in the outdoor
unit single phase or open phase
in the 3-phase power at one of
outdoor units in the group.
•
Reversed phase in the outdoor unit
single-phase or open phase in the
outdoor unit 3-phase power.
•
CT sensor is disconnected or there
is a problem with the circuit.
• Same at left
Reverse 2 phases of the outdoor unit
3-phase power and connect them
correctly.
Check that the CT sensor is not
disconnected, and make sure it is
inserted.
Fill up the gas appropriately.
L02
displayed
L13
displayed
Both the
Operation lamp
and Standby
lamp are blinking
simultaneously.
• Indoor-outdoor unit type mismatch.
• Same at left
• Same at left
—
C
heck that the indoor and outdoor unit
types are correct.
L07
displayed
—
—
•
Remote controller communication
wiring is connected to the indoor
unit, however it is set for individual
operation.
• Same at left
Perform automatic address setting
(See 2-8).
P09
displayed
Timer lamp and
Standby lamp
are blinking
alternately.
•
The indoor unit ceiling panel connector
is not connected correctly.
•
Ceiling panel connector at one of
the indoor units in the group is not
connected correctly.
•
Indoor unit ceiling panel connector
is not connected correctly.
• Same at left
Connect the indoor unit ceiling panel
connector correctly.
P12
displayed
• Indoor unit DC fan trouble.
•
DC fan trouble at one of the indoor
units in the group.
• Indoor unit fan trouble.
• Same at left
Check whether the fan holder is loose.
Check the wiring between the DC fan
and the PCB.
P15
displayed
Operation lamp
and Standby
lamp are blinking
alternately.
• No gas
• Same at left
• Same at left
—
Check the refrigerant cycle (for gas
leaks).
SM830160-03̲Classic̲PAC-i̲A4.ind4 4
SM830160-03̲Classic̲PAC-i̲A4.ind4 4
2010/02/16 10:28:08
2010/02/16 10:28:08
Содержание SPW-C256VH
Страница 364: ... MEMO 1 358 ...
Страница 398: ... MEMO 2 34 ...
Страница 402: ...3 4 3 3 1 Indoor Units 4 Way Air Discharge Semi Concealed Type SPW XM125 165 185H Electric Wiring Diagram 䡵 ...
Страница 403: ...3 5 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Electric Wiring Diagram 䡵 ...
Страница 404: ...3 6 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Schematic Diagram 䡵 ...
Страница 405: ...3 7 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Electric Wiring Diagram 䡵 ...
Страница 406: ...3 8 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Schematic Diagram 䡵 ...
Страница 409: ...3 11 3 3 1 Indoor Units Concealed Duct Type SPW UR124 164 184 254 364 484 604GH56 A B Electric Wiring Diagram 䡵 ...
Страница 410: ...3 12 3 3 1 Indoor Units Concealed Duct Type SPW UR124 164 184 254 364 484 604GH56 A B Schematic Diagram 䡵 ...
Страница 411: ...3 13 3 3 1 Indoor Units Concealed Duct Type SPW U125 165 185 255 365 485 605H Electric Wiring Diagram 䡵 ...
Страница 412: ...3 14 3 3 1 Indoor Units Concealed Duct Type SPW U125 165 185 255 365 485 605H Schematic Diagram 䡵 ...
Страница 415: ...3 17 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Electric Wiring Diagram 䡵 ...
Страница 416: ...3 18 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Schematic Diagram 䡵 ...
Страница 417: ...3 19 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256VH ...
Страница 419: ...3 21 3 3 2 Outdoor Units Electric Wiring Diagram SPW C366VH ...
Страница 421: ...3 23 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486VH ...
Страница 423: ...3 25 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256 366VH8 ...
Страница 425: ...3 27 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486 606VH8 ...
Страница 472: ... MEMO 6 10 ...
Страница 490: ... MEMO 7 18 ...
Страница 517: ...SANYO Electric Co Ltd Printed in Japan 201002E DC ...