2-16
X, T, U Types (for Link Wiring)
2-17. Caution
This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor unit,
and also in a system where 1 outdoor unit is connected to multiple indoor units (maximum 4 < Double-Twin >).
• This test run explanation describes primarily the procedure when using the wired remote controller.
• If link wiring is used, set the outdoor unit system address to allow the combination of indoor and outdoor units to
be identified. At the same time, indicate the indoor-outdoor unit combination number in a location where it can
be checked easily (near the indoor unit nameplates). (This number will be required for subsequent maintenance.
Refer to 2-22-2, -3, -4.)
• Request that the customer be present when the test run is performed. At this time, explain the operation manual
and have the customer perform the actual steps.
• Be sure to pass the manuals and warranty certificate to the customer.
• Check that the 220 - 240 V AC wiring is not connected to the inter-unit control wiring connector terminal.
If 220 - 240 V AC is accidentally applied, the indoor or outdoor unit control
PCB fuse (0.5 A for both indoor and outdoor units) will blow in order to
protect the PCB. Correct the wiring connections, then disconnect the 2P
connectors (indoor: blue, OC) (outdoor: blue, serial 1) that are connected
to the PCB, and replace them with 2P connectors (indoor: brown, EMG)
(outdoor: brown, serial 2). If operation is still not possible after changing the
brown connectors, try cutting the varistor (black) (both indoor and outdoor).
(Be sure to turn the power OFF before performing this work.)
ON
1
2
3
2 HP
DIP switch
(SW101)
Address switch
(SW102)
3 HP
DIP switch
(SW101)
Address switch
(SW102)
2-16-6. Indoor unit address setting
• If multiple single-type units are installed in the same room the addresses can be set to prevent signal interference.
By coordinating the numbers of the indoor unit (wireless PCB) and remote controller addresses, up to 6 indoor
units can be controlled independently by their respective remote controllers.
Independent control is not possible when a simultaneous operation multi system is used.
• Checking the addresses
Press the remote controller address button to display the current address on the remote controller display.
If this address matches the indoor unit (wireless PCB) address, the buzzer will sound.
(If ALL is set, the buzzer will always sound.) If ALL is set, operation is possible regardless of the indoor unit address.
Point the remote controller toward the receiver (indoor unit) that you wish to operate, and send the operation signal.
• Remote controller address setting
Press and hold the address button for 4 seconds or longer
to display the address on the remote controller display. The
current address starts blinking.
The address changes each time the remote controller
address button is pressed: ALL 1 2 3 ... 6.
Set the address to match the remote controller you wish
to operate. When the SET button is pressed, the address
stops blinking and displays for 5 seconds. The buzzer
sounds if the address matches the indoor unit.
12
3
6 5 4
3 2 1
ON
ON
OFF
12
3
6 5 4
3 2 1
ON
ON
OFF
12
3
6 5 4
3 2 1
ON
ON
OFF
12
3
6 5 4
3 2 1
ON
ON
OFF
Remote
controller
address
display
Indoor
unit PCB
address,
DIP switch
Address
Address
ALL
Address
1
Address
2
Address
3
Address
Address
Address
For address switches 1, 2, and 3, turn DIP switch 1 to OFF.
For address switches 4, 5, and 6, turn DIP switch 1 to ON.
Address switch
Test
Remote controller
Main Off
Sub On
Indoor unit control PCB
Fig. 2-14
Up side
HIC
Temperature
sensor
AUTO ADD (CN041)
System address
Rotary switch (S002)
TERMINAL (S010)
JP007
System address
DIP switch (S003)
RC-P (CN032,RED)
LED1
LED2
PUMP DOWN (CN042)
EEPROM (IC006)
TO (CN022, WHT)
Bottom
side
C2 (CN020, WHT)
MOV (CN25, WHT)
C1 (CN021, BLK)
TD, TS (CN023, WHT)
EXCT (CN026, RED)
SILENT (CN028, WHT)
RC-P (CN032, RED)
FAN (CN030, WHT)
ROM (CN012, WHT)
OC (CN013, BLU)
EMG (CN014, BRN)
20S (CN09, WHT)
FUSE (25A, F003)
SPW-C486VH
F101
MOV
(CN025, WHT)
TD (CN024, BLK)
TO (CN023, BLK)
TS (CN022, RED)
Varistor (VA002)
JP007
Varistor (VA001)
Terminal plug
(CN015, BLK)
EMG (CN014, BRN)
OC (CN013, BLU)
ROM (CN012, WHT)
EEPROM (IC007)
PRY (CN110, YEL)
C2 (CN020, WHT)
C1 (CN021, WHT)
SPW-C256/366VH
System address rotary switch
Terminal plug (CN015, BLK)
OC (CN013, BLU)
EMG (CN014, BRN)
JP007
ROM (CN012, WHT)
EEPROM (IC007)
TD (CN024, BLK)
TO (CN023, BLK)
MOV(CN025, WHT)
SPW-C256/366VH8
SPW-C486/606VH8
System address 10s digit and 20s digit
DIP switch
Automatic address
button (black)
Terminal plug (black)
C2 (CN020, WHT)
C1 (CN021, WHT)
TS (CN022, RED)
Fig. 2-15
Outdoor unit control PCB
CHK (2P plug)
2P connector (brown)
2P connector (blue)
Varistor (black)
VA100
Fuse 0.5A
Indoor unit control PCB
SM830160-03̲Classic̲PAC-i̲A4.ind16 16
SM830160-03̲Classic̲PAC-i̲A4.ind16 16
2010/02/16 10:28:11
2010/02/16 10:28:11
Содержание SPW-C256VH
Страница 364: ... MEMO 1 358 ...
Страница 398: ... MEMO 2 34 ...
Страница 402: ...3 4 3 3 1 Indoor Units 4 Way Air Discharge Semi Concealed Type SPW XM125 165 185H Electric Wiring Diagram 䡵 ...
Страница 403: ...3 5 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Electric Wiring Diagram 䡵 ...
Страница 404: ...3 6 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Schematic Diagram 䡵 ...
Страница 405: ...3 7 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Electric Wiring Diagram 䡵 ...
Страница 406: ...3 8 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Schematic Diagram 䡵 ...
Страница 409: ...3 11 3 3 1 Indoor Units Concealed Duct Type SPW UR124 164 184 254 364 484 604GH56 A B Electric Wiring Diagram 䡵 ...
Страница 410: ...3 12 3 3 1 Indoor Units Concealed Duct Type SPW UR124 164 184 254 364 484 604GH56 A B Schematic Diagram 䡵 ...
Страница 411: ...3 13 3 3 1 Indoor Units Concealed Duct Type SPW U125 165 185 255 365 485 605H Electric Wiring Diagram 䡵 ...
Страница 412: ...3 14 3 3 1 Indoor Units Concealed Duct Type SPW U125 165 185 255 365 485 605H Schematic Diagram 䡵 ...
Страница 415: ...3 17 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Electric Wiring Diagram 䡵 ...
Страница 416: ...3 18 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Schematic Diagram 䡵 ...
Страница 417: ...3 19 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256VH ...
Страница 419: ...3 21 3 3 2 Outdoor Units Electric Wiring Diagram SPW C366VH ...
Страница 421: ...3 23 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486VH ...
Страница 423: ...3 25 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256 366VH8 ...
Страница 425: ...3 27 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486 606VH8 ...
Страница 472: ... MEMO 6 10 ...
Страница 490: ... MEMO 7 18 ...
Страница 517: ...SANYO Electric Co Ltd Printed in Japan 201002E DC ...