Control of W-ECO MULTI SYSTEM
3
TD831077
III - 65
2. Optional Controller (simplified remote controller)
7
How to install the simplified remote controller
Do not supply power to the
unit or try to operate it until
the tubing and wiring to the
outdoor unit is completed.
No.
Accompanying parts
Q’ty
1
2
2
3
2
7
Accessories
When connecting the locally supplied three
core lead wires to the terminal block, check the
terminal numbers in the indoor unit to make
sure that the wires are correctly connected.
(The simplified remote controller is damaged if
220 / 240 V AC is applied.)
(4)
Fit the simplified remote controller to the tabs of
the back case and mount it.screw.
Simplified remote
controller
(comes with
200 mm wire)
Machine screws
M4
×
25
Wood screws
No.
Accompanying parts
Q’ty
4
2
5
3
6
1
Spacers
Wire joints
Installation manual
¶
Do not twist the control
wiring with the power
wiring or run it in the same
metal conduit, because
this may cause malfunc-
tion.
¶
Install the simplified
remote controller away
from sources of electrical
noise.
¶
Install a noise filter or take
other appropriate action if
electrical noise affects the
power supply circuit of the
unit.
The mounting position for the simplified remote control-
ler should be located in an accessible place for control.
Never cover over the simplified remote controller or
recess it into the wall.
(1)
Insert a screwdriver or the like in the groove on
the lower side of the simplified remote controller
body to pry off the back case.
When using a wall box for flush mounting
¶
If local codes allow, this weekly timer can be mounted
using a conventional wall box for flush mounting.
(2)
Use the two supplied M4 machine screws to
secure the simplified remote controller back case.
Prior to mounting, clear the cutouts in the back
case corresponding to the holes in the wall box
using a screwdriver or the like. Use the spacers
and take care not to tighten the screws exces-
sively. If the back case will not seat well, cut the
spacers to a suitable thickness.
(3)
Connect locally supplied three core lead wires to
the lead wires from the simplified remote control-
ler. (See “How to wire the simplified remote
controller.”)
1507_T_I
Simplified remote
controller
Under case (back case)
Spacer
Machine screws
M4
×
25 (2)
Electric junction box
for one box (no cover)
Wall
1506_T_I
Mounting dimensions for continuous installation
CAUTION
• Mount the simplified remote controller at a height of 1 to
1.5 meters above the floor where it can sense the aver-
age temperature of the room.
• Do not mount the simplified remote controller in a place
exposed to direct sunlight or a place exposed to outside
air such as near a window.
• Do not mount the simplified remote controller behind an
object so that it is separated from the air circulation of
the room.
• Mount the simplified remote controller in a room air con-
ditioned.
• The simplified remote controller must be mounted on the
wall or other surface vertically.
Place of installation
TEST
SET TEMP.
FAN SPEED
MODE
ON - / OFF -
FLAP
Spacer
1510_T_I
Wiring outlet
60
R2
70
13
16
JIS C8336
120
80
84
(18)