II - 27
2
TD831077
Design of W-ECO MULTI SYSTEM
4. Installation Instructions
Min. 50 cm
Min. 13 cm
Min. 50 cm
Min.
50 cm
Min. 60 cm
on the
valve side
1670_C_I
PC and AD unit placed adjacently
Out-
door
unit
Heat
source
Hot air
Exhaust fan
0024_C_I
4-4. Outdoor Unit
AVOID:
●
heat sources, exhaust fans, etc.
●
damp, humid or uneven locations.
●
Indoor (no ventilation place)
DO:
●
choose a place as cool as possible.
●
choose a place that is well ventilated.
●
allow enough room around the unit for air intake/ exhaust
and possible maintenance.
Installation space
Install the outdoor unit where there is enough space for
ventilation. Otherwise the unit may not operate properly. Fig.
2-10 shows the minimum space requirement around the
outdoor units when three sides are open and only one side is
shuttered, with areas over the unit open. The mounting base
should be concrete or a similar material that allows for
adequate drainage. Make provisions for anchor bolts,
platform height, and other site-specific installation require-
ments.
●
Not more than 2 units
should be installed
adjacently.
●
Leave space open above
the unit.
●
Construct louvers or other
openings in the wall, if
necessary, to ensure
adequate ventilation.
* Do not do any wiring or tubing within 60 cm of the front
panel, because it is needed as a servicing space for the
compressor.
Multiple installation
CAUTION
NOTE
One units in two row
1671_C_I
Min.
0.9 m
0.6 m
Min.
0.9 m
Min.
0.9 m
Min.
0.9 m
One units in three row
1672_C_I
Min.
1.1 m
0.6 m
0.6 m
Min.
1.1 m
Min.
1.1 m
Min.
1.1 m
Conditions for installation: Fence height 1.8m, Effective opening ratio 50%, No raising for installation.
The distances between the units will vary with changes in installation conditions.
Three sets by two rows (Total
six sets)
1675_C_I
Min.
1.6 m
1.5 m
Min.
1.6 m
Min.
1.6 m
0.66 m
0.66 m
Min.
1.6 m
Three sets by three rows
(Total nine sets)
1676_C_I
Min.
2.2 m
1.5 m
1.5 m
Min.
2.2 m
Min.
2.2 m
0.66 m
0.66 m
Min.
2.2 m
Two sets by two rows
(Total four sets)
1673_C_I
Min.
1.3 m
1.0 m
Min.
1.3 m
Min.
1.3 m
0.66 m
Min.
1.3 m
Two sets by three rows (Total
six sets)
1674_C_I
Min.
2.1 m
1.0 m
1.0 m
Min.
2.1 m
Min.
2.1 m
0.66 m
Min.
2.1 m