Control of W-ECO MULTI SYSTEM
3
TD831077
III - 47
2. Optional Controller (system controller)
(2)
Zone registration by system controller
❏
In this case you set all central addresses by system controller at once manually.
a
Press the TEST / CHK and ZONE buttons at the same time for more than 4 seconds.
SETTING
and CODE No. C1 will flush.
b
After confirming code No. C1, press the SET button.
Once in this mode, a change takes place as shown below.
SET
CL
MODE
FAN SPEED
FLAP
SET TEMP.
SELECT
CENTRAL
CTRL
GROUP
ZONE
R.C.
No.
UNIT No.
No.
CODE
ZONE
1
9
2
3
4
6
ON
OFF
•
•
TEST / CHK
ALL / ZONE / GR
SETTING
0203_M_I
Registed ZONE and GROUP
No. are displayed.
In case of No-registed,
number is not displayed.
In case of registed, UNIT No.
will be displayed.
: Selected GROUP No.
in case of No-registed.