IV - 133
TD831077
4
W-ECO MULTI SYSTEM Unit Specifications
Indoor unit (D)
MODEL No.
SPW-FMR253GH56
SPW-FM253GH56
Source
220 - 230 - 240 V / 1 phase / 50Hz
Controller P.C.B. Ass’y
CR-X253GH (Microprocessor)
Fan (Number…diameter)
mm
Centrifugal (2 … ø 153)
Fan motor
Model…Nominal output
W
KFG4Q-61C3P … 60 W
Source
220 - 230 - 240 V / 1 phase / 50 Hz
No. of pole…r.p.m. (230 V, High)
rpm.
4 … 1,066
Coil resistance
Ω
BRN – WHT : 67.62
ORG – YEL
: 17.36
(Ambient temperature 20
°
C)
WHT – VLT
: 18.47
YEL – PNK
:
5.18
VLT – ORG : 10.10
Safety device
Operating temperature
Open
°
C
130
±
5
Close
°
C
(115
±
5)
Run capacitor
VAC,
µ
F
440 VAC, 3.5
µ
F
Electronic expansion valve
Coil
DKV-MOZS550E0
Coil resistance (at 20
°
C)
Ω
ORG – GRY : 46 ,
YEL – GRY : 46
RED – GRY : 46 ,
BLK – GRY : 46
Valve body
IKV-24D12
Heat exchanger
Coil
Aluminum plate fin / Copper tube
Rows…fin pitch
mm
3 … 2.0
Face area
m
2
0.165
10. Concealed Floor-Standing Type (FM Type)