1
TD831077
I - 4
Outline of W-ECO MULTI SYSTEM
2. Features of W-ECO MULTI SYSTEM
2-1. Outline of system
W-ECO MULTI is capable of controlling the capacity by 1 H.P. up to 30 H.P. without inverter control.
7
W-ECO multi system
Up to 30 H.P. (84 kW)
Limitation of system
Allowable no. outdoor unit connected
2 units
Allowable max. capacity of outdoor unit 30 H.P. (84 kW)
Allowable No. of indoor unit connected
32 units
Indoor / outdoor unit capacity ratio
~ 130 %
1754_M_I
2 pipes
Connection
●
SANYO makes it possible to link
outdoor units together for a large
84 kW (30 H.P.) capacity (the largest in
the market).
Addition
●
If your indoor capacity load changes in the future, it’s easy to
add on both indoor and outdoor units using the same tubings.
Concentration
●
Since all tubings are
concentrated into one
pipe shaft, you can minimize
piping space and construction
labor.
¶
AD (Additional) unit can not be used independently.
¶
R407C model and R22 model must not be used as a combination outdoor unit.
CAUTION
7
Combination outdoor units
PC unit can be used independently or in combination with AD unit.
* When two outdoor units are used for one refrigerant circuit, be sure to use one PC unit and one AD unit, each.
NOTE
1 unit
2 units
2092
PC unit
1768_C_I
830
2092
925
90
(132)
PC unit
AD unit
1769_C_I
830
Design your outdoor unit however you want by combining power contorl units and AD units (up to 2 units) for a horsepower
of up to 30 HP. And since you can set the unit capacity to match the indoor load, you can design your air conditioning
system much more freely than before, as well as reduce your initial costs by designing the system just the way you want it.
Combination of outdoor units
1 unit
2 units
Cooling capacity
kW (HP)
45 (16)
56 (20)
67.4 (24)
73 (26)
78.4 (28)
84 (30)
150 type
1
1
1
190 type
1
1
1
70 type
1
1
90 type
1
1
No. of units to be combined
Power control
outdoor unit
(capacity control possible)
1735_C_I
1735_C_I
1734_C_I
AD outdoor unit