Control of W-ECO MULTI SYSTEM
3
TD831077
III - 50
■
How to check overlapping of central address No.
a
Press the TEST / CHK and ZONE buttons at the same time for more than 4 seconds.
SETTING
and CODE No. C1 will flash.
b
Select CODE No. C3 by pressing
,
(SET TEMP) button and press the SET button.
C3 changes from flashing to ON state and
SETTING
will flash. Then auto. overlap checking will start.
c
If C3 changes from ON to flashing and
SETTING
changes from flashing to ON, there is no overlapping. Then finally,
complete the auto. overlap checking mode by pressing the TEST / CHK button.
d
If some of GROUP No., ZONE No. and UNIT No. flash, you should try again the zone registration.
1
Select CODE No. C1 by pressing
,
(SET TEMP) button and press the SET button.
2
Select the flashing GROUP No. with ZONE and GROUP button.
Then press the CL button and re-select the ZONE, GROUP and UNIT No.
3
Then finally, complete the auto. overlap checking mode by pressing the TEST / CHK button.
2. Optional Controller (system controller)
SET
CL
MODE
FAN SPEED
FLAP
SET TEMP.
SELECT
CENTRAL
CTRL
GROUP
ZONE
R.C.
No.
UNIT No.
No.
CODE
ZONE
1
9
2
3
4
6
ON
OFF
•
•
TEST / CHK
ALL / ZONE / GR
SETTING
0205_M_I
Registed ZONE and GROUP
No. are displayed.
In case of No-registed,
number is not displayed.
In case of registed, UNIT No.
will be displayed.
: Selected GROUP No.
in case of No-registed.