Control of W-ECO MULTI SYSTEM
3
TD831077
III - 27
2. Optional Controller (remote controller)
i
Select the code No. 14 to set group setting with the
,
(SET TEMP) button.
j
Set the No. of group setting as shown below with the
,
(
) button.
0 : Standard system (except group control)
1 : Main indoor unit in case of group control
2 : Sub indoor unit in case of group control
99 : No setting (at factory shipment)
k
Press the SET button.
UNIT No., CODE No. 14,
SETTING
and SET DATA change from flashing to ON state.
l
If you make mistake, press the CL button so that setting changes the initial state.
m
Press the TEST / CHK button to finish this mode.
The display is disappeared.
n
Confirm the indoor unit address (UNIT No.) with the UNIT button after pressing the ON / OFF button.
o
Finally, remove the short circuit of DISP PIN.
And in case of group control, be sure to restore the branch wiring to its original wiring. In case of remote controller–
less system, remove the remote controller.