2. Processes and functions
Fig. 9
2-6
Condensing Temperature Control (Cooling)
Condensing temperature is controlled by the outdoor heat exchanger coil temperature as
sensed by sensor C2.
Chart Explanations and notes
❑
This chart shows how the outdoor fan speed and the electronic refrigerant control valve
react to coil temperature to control condensing temperature.
❑
Sensor C2 is located in the middle of the outdoor unit heat exchange coil.
❑
When C2 rises above 140°F the electronic refrigerant control valve opens at 50 steps/30
seconds, and the outdoor fan speed is forced to change to high (H) until C2 falls below
131°F.
140
131
OUTDOOR UNIT
COIL TEMP. C2
(
°
F)
OUTDOOR FAN
SPEED
ELECTRONIC REF.
CONTROL VALVE
H, M or L
H, M or L
FORCED
H
1926_THS_I
OPEN