I - 59
SM830082
1
2
3
4
5
1. Specifications
Indoor Unit: TH3642
Outdoor Unit: CH3642
• 230V / 1 phase / 60Hz
RATING CAPACITY :
34,000 BTU/h
AIR FLOW RATE:
900 CFM
EVAPORATOR
CONDENSER
ENT.TEMP.
°
F(
°
C)
AMBIENT TEMP
°
F(
°
C)
WB
DB
75
85
95
105
115
(23.9)
(29.4)
(35.0)
(40.6)
(46.1)
TC
34,440
32,780
30,870
28,730
26,350
CI
2.32
2.53
2.76
3.06
3.36
72(22.2)
SHC
24,970
24,120
23,160
22,110
20,970
59
76(24.4)
SHC
28,140
27,290
26,330
25,280
24,140
(15.0)
80(26.7)
SHC
31,460
30,610
29,650
28,600
26,350
84(28.9)
SHC
34,440
32,780
30,870
28,730
26,350
88(31.1)
SHC
34,440
32,780
30,870
28,730
26,350
TC
35,730
34,140
32,440
30,500
28,390
CI
2.34
2.57
2.8
3.11
3.42
72(22.2)
SHC
21,060
20,310
19,520
18,640
17,710
63
76(24.4)
SHC
24,230
23,480
22,690
21,810
20,880
(17.2)
80(26.7)
SHC
27,540
26,800
26,010
25,130
24,190
84(28.9)
SHC
30,720
29,970
29,180
28,300
27,370
88(31.1)
SHC
33,890
33,140
32,350
30,500
28,390
TC
37,090
35,630
# 34,000
32,200
30,230
CI
2.36
2.59
2.83
3.14
3.45
72(22.2)
SHC
17,120
16,500
15,810
15,060
14,250
67
76(24.4)
SHC
20,300
19,670
18,980
18,230
17,420
(19.4)
80(26.7)
SHC
23,610
22,980
22,290
21,550
20,740
84(28.9)
SHC
26,780
26,160
25,470
24,720
23,910
88(31.1)
SHC
29,960
29,330
28,640
27,890
27,080
TC
39,070
37,710
36,240
34,650
32,880
CI
2.39
2.62
2.87
3.19
3.5
72(22.2)
SHC
13,220
12,690
12,120
11,520
10,850
71
76(24.4)
SHC
16,400
15,860
15,290
14,690
14,020
(21.7)
80(26.7)
SHC
19,710
19,180
18,610
18,000
17,340
84(28.9)
SHC
22,880
22,350
21,780
21,180
20,510
88(31.1)
SHC
26,060
25,520
24,950
24,350
23,680
TC
39,850
38,560
37,200
35,630
33,970
CI
2.43
2.66
2.91
3.23
3.55
75
76(24.4)
SHC
12,170
11,720
11,240
10,700
10,140
(23.9)
80(26.7)
SHC
15,490
15,030
14,560
14,020
13,460
84(28.9)
SHC
18,660
18,200
17,730
17,190
16,630
88(31.1)
SHC
21,830
21,380
20,900
20,360
19,800
TC :Total Cooling Capacity (BTU/h)
SHC:Sensible Heat Capacity (BTU/h)
CI :Compressor Input (kW)
Rating conditions are
M.R.=
10.68
USpints/h
:Outdoor Ambient Temp.95
°
FDB
:Indoor Unit Entering Air Temp.80
°
FDB/67
°
FWB