2. Processes and functions
Fig. 10
2-7
Overload Protection (Heating)
This function prevents the air conditioner from overloading.
Chart Explanations and notes
❑
This chart shows how the outdoor fan speed and the electronic refrigerant control valve
react to coil temperature to keep the indoor heat exchanger coil from overloading.
❑
When sensor E2 rises above 140°F the electronic refrigerant control valve opens at 50
steps/30 seconds until E2 falls below 138°F.
❑
Sensor E2 is located in the middle of the indoor unit heat exchange unit.
❑
When sensor E2 rises above 144°F, the control circuit stops the outdoor fan motor till the
temp. drops to 131°F
❑
Fuzzy control controls the electronic refrigerant control valve.
(
°
F)
ELECTRONIC REF.
CONTROL VALVE
INDOOR UNIT COIL
TEMP. (E2)
147
144
140
138
131
127
OUTDOOR FM
START UP
COMPENSATION
OFF
OPEN
H OR M
H OR M
H
L
1927_THS_I
FUZZY CONTROL
FUZZY CONTROL
OVERLOAD
PROTECTION
OVERLOAD PROTECTION
OPEN