I - 116
SM830082
1
2
3
4
5
1. Specifications
Cooling:
Rating Conditions
: Indoor Air Temperature
80
°
F DB / 67
°
F WB
Outdoor Air Temperature
95
°
F DB
Full Load Conditions : Indoor Air Temperature
80
°
F DB / 67
°
F WB
Outdoor Air Temperature 115
°
F DB
Heating:
Rating Conditions
: Indoor Air Temperature
70
°
F DB / 60
°
F WB
Outdoor Air Temperature
47
°
F DB / 43
°
F WB
Full Load Conditions : Indoor Air Temperature
80
°
F DB / —
°
F WB
Outdoor Air Temperature
45
°
F DB / 35
°
F WB
Indoor model: KH3642 / Outdoor model: CH3642
●
Cooling
●
Heating
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
230 - 208 V / 1 phase / 60 Hz
230 - 208 V / 1 phase / 60 Hz
Rating conditions
A
0.5 - 0.5
1.8 - 1.8
12.6 - 13.2
14.9 - 15.5
kW
0.10 - 0.09
0.36 - 0.34
2.83 - 2.69
3.29 - 3.12
Full load conditions
A
0.5 - 0.5
1.8 - 1.8
15.4 - 16.8
17.7 - 19.1
kW
0.10 - 0.09
0.36 - 0.34
3.45 - 3.38
3.91 - 3.81
Starting amperes
A
1 - 1
2 - 2
95 - 86
97.5 - 88.5
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
230 - 208 V / 1 phase / 60 Hz
230 - 208 V / 1 phase / 60 Hz
Rating conditions
A
0.5 - 0.5
1.8 - 1.8
15.5 - 16.8
17.8 - 19.1
kW
0.10 - 0.09
0.36 - 0.34
3.40 - 3.38
3.86 - 3.81
Full load conditions
A
0.5 - 0.5
1.8 - 1.8
14.7 - 16.0
17 - 18.3
kW
0.10 - 0.09
0.36 - 0.34
3.32 - 3.29
3.78 - 3.72
Starting amperes
A
1 - 1
2 - 2
95 - 86
97.5 - 88.5