I - 65
SM830082
1
2
3
4
5
1. Specifications
Indoor Unit: UH3642
Outdoor Unit: CH3642
• 230V / 1 phase / 60Hz
RATING CAPACITY :
34,500 BTU/h
AIR FLOW RATE:
1,060 CFM
EVAPORATOR
CONDENSER
ENT.TEMP.
°
F(
°
C)
AMBIENT TEMP
°
F(
°
C)
WB
DB
75
85
95
105
115
(23.9)
(29.4)
(35.0)
(40.6)
(46.1)
TC
34,950
33,260
31,330
29,150
26,740
CI
2.32
2.53
2.76
3.06
3.36
72(22.2)
SHC
26,210
25,370
24,440
23,400
22,280
59
76(24.4)
SHC
29,810
28,970
28,040
27,000
25,880
(15.0)
80(26.7)
SHC
33,570
32,740
31,330
29,150
26,740
84(28.9)
SHC
34,950
33,260
31,330
29,150
26,740
88(31.1)
SHC
34,950
33,260
31,330
29,150
26,740
TC
36,260
34,640
32,910
30,950
28,810
CI
2.34
2.57
2.8
3.11
3.42
72(22.2)
SHC
21,860
21,130
20,360
19,500
18,580
63
76(24.4)
SHC
25,460
24,730
23,960
23,100
22,180
(17.2)
80(26.7)
SHC
29,230
28,490
27,720
26,860
25,940
84(28.9)
SHC
32,830
32,090
31,320
30,460
28,810
88(31.1)
SHC
36,260
34,640
32,910
30,950
28,810
TC
37,640
36,160
# 34,500
32,670
30,670
CI
2.36
2.59
2.83
3.14
3.45
72(22.2)
SHC
17,500
16,890
16,210
15,470
14,680
67
76(24.4)
SHC
21,100
20,490
19,810
19,070
18,280
(19.4)
80(26.7)
SHC
24,860
24,250
23,570
22,840
22,050
84(28.9)
SHC
28,460
27,850
27,170
26,440
25,650
88(31.1)
SHC
32,060
31,450
30,770
30,040
29,250
TC
39,640
38,260
36,780
35,160
33,360
CI
2.39
2.62
2.87
3.19
3.5
72(22.2)
SHC
13,150
12,620
12,070
11,480
10,820
71
76(24.4)
SHC
16,750
16,220
15,670
15,080
14,420
(21.7)
80(26.7)
SHC
20,510
19,990
19,440
18,840
18,190
84(28.9)
SHC
24,110
23,590
23,040
22,440
21,790
88(31.1)
SHC
27,710
27,190
26,640
26,040
25,390
TC
40,430
39,120
37,740
36,160
34,470
CI
2.43
2.66
2.91
3.23
3.55
75
76(24.4)
SHC
12,100
11,650
11,190
10,660
10,110
(23.9)
80(26.7)
SHC
15,860
15,420
14,950
14,430
13,870
84(28.9)
SHC
19,460
19,020
18,550
18,030
17,470
88(31.1)
SHC
23,060
22,620
22,150
21,630
21,070
TC :Total Cooling Capacity (BTU/h)
SHC:Sensible Heat Capacity (BTU/h)
CI :Compressor Input (kW)
Rating conditions are
M.R.=
9.97
USpints/h
:Outdoor Ambient Temp.95
°
FDB
:Indoor Unit Entering Air Temp.80
°
FDB/67
°
FWB