1. Specifications
1
1
2
3
4
5
I - 114
SM830080
1-11 Installation Instructions
Electrical Characteristics
Indoor Unit : SPW-TR483GH56
Outdoor Unit : SPW-CR483GHL8
SPW-CR483GL8
●
Cooling
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
220 - 240 V / 1 phase / 50 Hz
380 - 415 V / 3 phase / 50 Hz
Rating conditions
A
0.95 / 0.98
1.24 / 1.31
7.7 / 7.72
8.35 / 8.38
kW
200 / 220
0.26 / 0.29
4.14 / 4.16
4.6 / 4.67
Full load conditions
A
0.95 / 0.98
1.24 / 1.31
8.8 / 8.82
9.47 / 9.5
kW
200 / 220
0.26 / 0.29
5 / 5.04
5.46 / 5.55
Starting amperes
A
2 / 2
3 / 3
48 / 53
53 / 58
●
Heating (Heat pump only)
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
220 - 240 V / 1 phase / 50 Hz
380 - 415 V / 3 phase / 50 Hz
Rating conditions
A
0.86 / 0.9
1.24 / 1.31
8.89 / 8.91
9.54 / 9.56
kW
180 / 200
0.26 / 0.29
5.06 / 5.08
5.5 / 5.57
Full load conditions
A
0.86 / 0.9
1.24 / 1.31
9.4 / 9.41
10.05 / 10.07
kW
180 / 200
0.26 / 0.29
5.38 / 5.42
5.82 / 5.91
Starting amperes
A
2 / 2
3 / 3
48 / 53
53 / 58
Cooling:
Rating Conditions
:
Indoor Air Temperature
27
°
C DB / 19
°
C WB
Outdoor Air Temperature 35
°
C DB
Full Load Conditions
:
Indoor Air Temperature
35
°
C DB / 23
°
C WB
Outdoor Air Temperature 43
°
C DB
Heating:
Rating Conditions
:
Indoor Air Temperature
20
°
C DB
Outdoor Air Temperature
7
°
C DB / 6
°
C WB
Full Load Conditions
:
Indoor Air Temperature
24
°
C DB
Outdoor Air Temperature 21
°
C DB / 15.5
°
C WB