1. Specifications
1
2
3
4
5
I - 113
SM830080
1-11 Installation Instructions
Electrical Characteristics
Indoor Unit : SPW-TR363GH56
Outdoor Unit : SPW-CR363GHL8
SPW-CR363GL8
●
Cooling
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
220 - 240 V / 1 phase / 50 Hz
380 - 415 V / 3 phase / 50 Hz
Rating conditions
A
0.95 / 0.98
1.24 / 1.31
6.35 / 6.39
7.01 / 7.06
kW
200 / 220
0.26 / 0.29
3.46 / 3.51
3.92 / 4.02
Full load conditions
A
0.95 / 0.98
1.24 / 1.31
7.2 / 7.24
7.86 / 7.91
kW
200 / 220
0.26 / 0.29
3.98 / 4.02
4.44 / 4.53
Starting amperes
A
2 / 2
3 / 3
42 / 45
47 / 50
●
Heating (Heat pump only)
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
220 - 240 V / 1 phase / 50 Hz
380 - 415 V / 3 phase / 50 Hz
Rating conditions
A
0.86 / 0.9
1.24 / 1.31
7 / 7.04
7.64 / 7.68
kW
180 / 200
0.26 / 0.29
3.86 / 3.88
4.3 / 4.37
Full load conditions
A
0.86 / 0.9
1.24 / 1.31
7.4 / 7.44
8.04 / 8.09
kW
180 / 200
0.26 / 0.29
4.08 / 7.12
4.52 / 4.61
Starting amperes
A
2 / 2
3 / 3
42 / 45
47 / 50
Cooling:
Rating Conditions
:
Indoor Air Temperature
27
°
C DB / 19
°
C WB
Outdoor Air Temperature 35
°
C DB
Full Load Conditions
:
Indoor Air Temperature
35
°
C DB / 23
°
C WB
Outdoor Air Temperature 43
°
C DB
Heating:
Rating Conditions
:
Indoor Air Temperature
20
°
C DB
Outdoor Air Temperature
7
°
C DB / 6
°
C WB
Full Load Conditions
:
Indoor Air Temperature
24
°
C DB
Outdoor Air Temperature 21
°
C DB / 15.5
°
C WB