1. Specifications
1
1
2
3
4
5
I - 122
SM830080
1-11 Installation Instructions
Electrical Characteristics
Indoor Unit : SPW-DR483GH56
Outdoor Unit : SPW-CR483GHL8
SPW-CR483GL8
●
Cooling
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
220 - 240 V / 1 phase / 50 Hz
380 - 415 V / 3 phase / 50 Hz
Rating conditions
A
2.8 / 3
1.24 / 1.31
7.7 / 7.72
8.87 / 8.92
kW
600 / 710
0.26 / 0.29
4.14 / 4.16
5 / 5.16
Full load conditions
A
2.8 / 3
1.24 / 1.31
8.8 / 8.82
10.02 / 10.06
kW
600 / 710
0.26 / 0.29
5 / 5.04
5.86 / 6.04
Starting amperes
A
4 / 4
3 / 3
48 / 53
55 / 60
●
Heating (Heat pump only)
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
220 - 240 V / 1 phase / 50 Hz
380 - 415 V / 3 phase / 50 Hz
Rating conditions
A
2.8 / 3
1.24 / 1.31
8.89 / 8.91
10.11 / 10.15
kW
600 / 710
0.26 / 0.29
5.06 / 5.08
5.92 / 6.08
Full load conditions
A
2.8 / 3
1.24 / 1.31
9.4 / 9.41
10.62 / 10.66
kW
600 / 710
0.26 / 0.29
5.38 / 5.42
6.24 / 6.42
Starting amperes
A
4 / 4
3 / 3
48 / 53
55 / 60
Cooling:
Rating Conditions
:
Indoor Air Temperature
27
°
C DB / 19
°
C WB
Outdoor Air Temperature 35
°
C DB
Full Load Conditions
:
Indoor Air Temperature
35
°
C DB / 23
°
C WB
Outdoor Air Temperature 43
°
C DB
Heating:
Rating Conditions
:
Indoor Air Temperature
20
°
C DB
Outdoor Air Temperature
7
°
C DB / 6
°
C WB
Full Load Conditions
:
Indoor Air Temperature
24
°
C DB
Outdoor Air Temperature 21
°
C DB / 15.5
°
C WB