1. Specifications
1
1
2
3
4
5
I - 10
SM830080
1-1
Unit Specifications
Ceiling Mounted Type
MODEL No.
Indoor Unit
SPW-TR253GH56
Outdoor Unit
SPW-CR253GL5
POWER SOURCE
220 - 230 - 240 V / 1 phase / 50 Hz
PERFORMANCE
Cooling
Capacity
kW
7.3
BTU / h
25,000
Air circulation (Hi / Me / Lo)
m
3
/h
1,080 / 960 / 840
Moisture removal (High)
Liters/h
3.5
ELECTRICAL RATINGS
Voltage rating
V
220
230
240
Available voltage range
V
198 – 264
Running amperes*
A
13.15
13.27
13.38
Max. running amperes**
A
14.49
14.53
14.56
Power input
kW
2.77
2.89
2.95
Power factor
%
95.7
94.7
91.9
C.O.P
W / W
2.64
2.53
2.47
Max. starting amperes
A
69
72
75
FEATURES
Controls / Thermostat control
Microprocessor / I.C. thermostat
Timer
ON / OFF 72-hours
ON/OFF 24-hours & Program
Fan speeds Indoor / Outdoor
3 and Automatic control / 3 (Auto)
Airflow direction (Indoor)
Automatic (Remote control)
Air filter
Washable, easy access, long life (2,500 hr)
Remote controller (Option)
Wired : RCS-SH80TG
Wireless : RCS-5PS3EWL
Refrigerant control
Electronic expansion valve
Drain pump (Drain connection)
No (20A, OD26 mm)
Compressor
Rotary (Sanyo)
Operation sound
Indoor - Hi/Me/Lo
dB - A
39 / 37 / 34
Outdoor - Hi
dB - A
52
Color (Approximate value)
Indoor
Munsell 10Y9.3 / 0.4, RAL 9010-GL
Outdoor
Munsell 5Y8.4 / 0.5, RAL 9002-GL
REFRIGERANT TUBING
Limit of tubing length
m (ft.)
50 (164 )
Limit of tubing length at shipment
m (ft.)
30 ( 98 )
Limit of elevation difference
m (ft.)
Outdoor unit is higher than indoor unit : 50 (164)
between the two units
Outdoor unit is lower than indoor unit : 30 (98)
Refrigerant tube
Narrow tube
mm (in.)
6.35 (1 / 4)
outer diameter
Wide tube
mm (in.)
15.88 (5 / 8)
Refrigerant amount at shipment
kg
R407C - 3.2
DIMENSIONS & WEIGHT
Indoor unit
Outdoor unit
Unit dimensions
Height
mm (in.)
190 ( 7 - 15 / 32)
735 (28 - 30 / 32)
Width
mm (in.)
1,300 ( 51 - 6 / 32)
940 (37
)
Depth
mm (in.)
670 ( 26 - 12 / 32)
340 (13 - 12 / 32)
Package dimensions
Height
mm (in.)
266 ( 10 - 15 / 32)
826 (32 - 17 / 32)
Width
mm (in.)
1,403 ( 55 - 8 / 32)
1,016 (40
)
Depth
mm (in.)
789 ( 31 - 2 / 32)
416 (16 - 12 / 32)
Net weight
kg (lb.)
26 ( 57 )
69 ( 152 )
Shipping weight
kg (lb.)
32 ( 71 )
75 ( 165 )
Shipping volume
m
3
(cu. ft)
0.294 (10.4)
0.349 (12.3)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Cooling:
Rating conditions (*):
Indoor air temperature 27
°
C DB / 19
°
C WB, Outdoor air temperature 35
°
C DB
Full load conditions (**): Indoor air temperature 32
°
C DB / 23
°
C WB, Outdoor air temperature 43
°
C DB