1. Specifications
1
2
3
4
5
I - 111
SM830080
1-11 Installation Instructions
Electrical Characteristics
Indoor Unit : SPW-TR253GH56
Outdoor Unit : SPW-CR253GHL5
SPW-CR253GL5
Cooling:
Rating Conditions
:
Indoor Air Temperature
27
°
C DB / 19
°
C WB
Outdoor Air Temperature 35
°
C DB
Full Load Conditions
:
Indoor Air Temperature
35
°
C DB / 23
°
C WB
Outdoor Air Temperature 43
°
C DB
Heating:
Rating Conditions
:
Indoor Air Temperature
20
°
C DB
Outdoor Air Temperature
7
°
C DB / 6
°
C WB
Full Load Conditions
:
Indoor Air Temperature
24
°
C DB
Outdoor Air Temperature 21
°
C DB / 15.5
°
C WB
●
Cooling
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
220 - 240 V / 1 phase / 50 Hz
380 - 415 V / 1 phase / 50 Hz
Rating conditions
A
0.43 / 0.43
0.62 / 0.65
12.1 / 12.3
13.15 / 13.38
kW
90 / 100
0.13 / 0.15
2.55 / 2.7
2.77 / 2.95
Full load conditions
A
0.43 / 0.43
0.62 / 0.65
13.44 / 13.48
14.49 / 14.56
kW
90 / 100
0.13 / 0.15
2.8 / 2.88
3.02 / 3.13
Starting amperes
A
1 / 1
1 / 1
67 / 73
69 / 75
●
Heating (Heat pump only)
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
220 - 240 V / 1 phase / 50 Hz
380 - 415 V / 1 phase / 50 Hz
Rating conditions
A
0.33 / 0.34
0.62 / 0.65
13.7 / 13.5
14.65 / 14.49
kW
70 / 80
0.13 / 0.15
2.86 / 2.96
3.06 / 3.19
Full load conditions
A
0.33 / 0.34
0.62 / 0.65
15.6 / 15.2
16.55 / 16.19
kW
70 / 80
0.13 / 0.15
3.25 / 3.29
3.45 / 3.52
Starting amperes
A
1 / 1
1 / 1
67 / 73
69 / 75