1. Specifications
1
2
3
4
5
I - 19
SM830080
1-1
Unit Specifications
Concealed Duct High Static Pressure Type
MODEL No.
Indoor Unit
SPW-DR253GH56
Outdoor Unit
SPW-CR253GL8
POWER SOURCE
380 - 400 - 415 V / 3N / 50 Hz
PERFORMANCE
Cooling
Capacity
kW
7.3
BTU / h
25,000
Air circulation (Hi / Me / Lo)
m
3
/h
1,380 / 1,320 / 1,260
Moisture removal (High)
Liters/h
3.1
External static pressure (High)
mmAq(Pa)
19 (186) : at shipment
ELECTRICAL RATINGS
Voltage rating
V
380
400
415
Available voltage range
V
342 – 456
Running amperes*
A
5.3
5.24
5.19
Max. running amperes**
A
6.15
6.14
6.14
Power input
kW
3.11
3.16
3.2
Power factor
%
89.2
87
85.8
C.O.P
W / W
2.35
2.31
2.28
Max. starting amperes
A
29
31
32
FEATURES
Controls / Thermostat control
Microprocessor / I.C. thermostat
Timer
ON / OFF 72-hours
Fan speeds Indoor / Outdoor
3 and Automatic control / 3 (Auto)
Airflow direction (Indoor)
—
Air filter
Field supply
Remote controller (Option)
Wired : RCS-SH80TG
Refrigerant control
Electronic expansion valve
Drain pump (Drain connection)
No (25A, OD32 mm)
Compressor
Rotary (Sanyo)
Operation sound
Indoor - Hi/Me/Lo
dB - A
44 / 43 / 42
Outdoor - Hi
dB - A
52
Color (Approximate value)
Indoor
—
Outdoor
Munsell 5Y8.4 / 0.5, RAL 9002-GL
REFRIGERANT TUBING
Limit of tubing length
m (ft.)
50 (164 )
Limit of tubing length at shipment
m (ft.)
30 ( 98 )
Limit of elevation difference
m (ft.)
Outdoor unit is higher than indoor unit : 50 (164)
between the two units
Outdoor unit is lower than indoor unit : 30 (98)
Refrigerant tube
Narrow tube
mm (in.)
6.35 (1 / 4)
outer diameter
Wide tube
mm (in.)
15.88 (5 / 8)
Refrigerant amount at shipment
kg
R407C - 3.2
DIMENSIONS & WEIGHT
Indoor unit
Outdoor unit
Unit dimensions
Height
mm (in.)
420 ( 16 - 17 / 32)
735 (28 - 30 / 32)
Width
mm (in.)
1,065 ( 41 - 30 / 32)
940 (37
)
Depth
mm (in.)
620 ( 24 - 13 / 32)
340 (13 - 12 / 32)
Package dimensions
Height
mm (in.)
513 ( 20 - 6 / 32)
826 (32 - 17 / 32)
Width
mm (in.)
1,148 ( 45 - 6 / 32)
1,016 (40
)
Depth
mm (in.)
713 ( 28 - 2 / 32)
416 (16 - 12 / 32)
Net weight
kg (lb.)
47 ( 104 )
69 ( 152 )
Shipping weight
kg (lb.)
61 ( 134 )
75 ( 165 )
Shipping volume
m
3
(cu. ft)
0.42 (14.8)
0.349 (12.3)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Cooling:
Rating conditions (*):
Indoor air temperature 27
°
C DB / 19
°
C WB, Outdoor air temperature 35
°
C DB
Full load conditions (**): Indoor air temperature 32
°
C DB / 23
°
C WB, Outdoor air temperature 43
°
C DB