1. Specifications
1
2
3
4
5
I - 119
SM830080
1-11 Installation Instructions
Electrical Characteristics
Indoor Unit : SPW-DR253GH56
Outdoor Unit : SPW-CR253GHL5
SPW-CR253GL5
●
Cooling
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
220 - 240 V / 1 phase / 50 Hz
380 - 415 V / 1 phase / 50 Hz
Rating conditions
A
2.29 / 2.31
0.62 / 0.65
12.1 / 12.3
15.01 / 15.26
kW
480 / 530
0.13 / 0.15
2.55 / 2.7
3.16 / 3.38
Full load conditions
A
2.29 / 2.31
0.62 / 0.65
13.44 / 13.48
16.35 / 16.44
kW
480 / 530
0.13 / 0.15
2.8 / 2.88
3.41 / 3.56
Starting amperes
A
3 / 3
1 / 1
67 / 73
71 / 77
●
Heating (Heat pump only)
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
220 - 240 V / 1 phase / 50 Hz
380 - 415 V / 1 phase / 50 Hz
Rating conditions
A
2.29 / 2.31
0.62 / 0.65
13.7 / 13.5
16.61 / 16.46
kW
480 / 530
0.13 / 0.15
2.86 / 2.96
3.47 / 3.64
Full load conditions
A
2.29 / 2.31
0.62 / 0.65
15.6 / 15.2
18.51 / 18.16
kW
480 / 530
0.13 / 0.15
3.25 / 3.29
3.86 / 3.97
Starting amperes
A
3 / 3
1 / 1
67 / 73
71 / 77
Cooling:
Rating Conditions
:
Indoor Air Temperature
27
°
C DB / 19
°
C WB
Outdoor Air Temperature 35
°
C DB
Full Load Conditions
:
Indoor Air Temperature
35
°
C DB / 23
°
C WB
Outdoor Air Temperature 43
°
C DB
Heating:
Rating Conditions
:
Indoor Air Temperature
20
°
C DB
Outdoor Air Temperature
7
°
C DB / 6
°
C WB
Full Load Conditions
:
Indoor Air Temperature
24
°
C DB
Outdoor Air Temperature 21
°
C DB / 15.5
°
C WB