Fig 4- 40 Floor linkage - type output
The equation above can be explained:
Note:
For the Type Output mode, no time delay is allowed.
Fig 4- 41 Floor linkage - point output
The figure shown above is the floor linkage of point output type and certain floor in the
system can be selected by drop-down box, which means The alarm of detector or module of any
specified type at the floor will cause the modules listed in the result list to act.
If any one of optical smoke detector or heat detector or MCP is triggered, the broadcast
and remote alarm devices at the same or immediately above/below floors with the
detector or MCP will all be activated.